Description of LED indicator status  20  and  21  for programmable outlets 1 and 2:
OFF: the outlets are not supplied with power.
Flashing: status change in progress.
ON: the outlets are supplied with power.
Outlets 1 and 2 can be remotely programmed and controlled. 
They may be used for sequential start-up of the protected applications, shedding of non-priority applications during
operation on battery power, and priority management at the end of battery backup time to reserve the longest possible
backup time for the most sensitive applications. These outlets are programmed using Solution Pac software.
LEDs  24  to  27  provide three
different indications:
1. Remaining backup time in percent
(during normal operation).
2. Percent load drawn by the protected
equipment, when button  23 is pressed.
3. Operating faults (flashing LED and
beeps):
27 Overload.
26  UPS fault.
25 Battery fault or end of life warning.
24 Site wiring Fault
3.2 LED indicators
CAUTION:The AC input power source must be present when
energizing for the first time.
1. Press the ON / OFF button  16 .
The buzzer beeps and all the LEDs go ON.
The buzzer beeps twice, then:
If AC input power is available, LED  18 goes ON, indicating    
operation in ON-LINE mode.
If AC input power is not available and the UPS is configured for 
automatic restart mode, the buzzer beeps three times and LED  17
goes ON, signalling operation on battery power.
All connected equipment is energized.
NOTE: If LEDs  17 or  18 do not turn ON or if LEDs  25 to  27 flash,
there is a fault (see section 4.1).
3.1 Start-up
3. Operation
The protected equipment connected to the UPS can be energized, whether AC input power is available or not.