2.5.3
Control Cable Connections
1. Feed the control cables into the inverter via one of the gland holes at the I/O
module end of the terminal housing.
2. Run the control cable underneath the I/O board toward the control terminals.
3. Connect the control wires in accordance with the terminal information given in
3. Connect the control wires in accordance with the terminal information given in
Figure 2-11.
4. Use screened cable for all control wiring.
8 9
1 2 3 4 5 6 7
Terminal Inputs Parameter
Default
operation
1
DIN 1
P0701 = ‘1’
ON/OFF1
2
DIN 2
P0702 = ‘12’
Reverse
3
DIN 3
P0703 = ‘9’
Fault Acknowledge
6/7
AIN (-/+)
P0756 = 0
0 – 10 V Analogue Input
Option: DIN 4
P0704
≠
0
8/9
Output Relay
P0731 = ’52.3’
Fault identification
Figure 2-11 Control Terminals
NOTE
If a PTC resistor is fitted, this
should be connected between 4
(+24 V) and 3 (DIN 3).
should be connected between 4
(+24 V) and 3 (DIN 3).