Siemens 6ED1050-1AA00-0BE8 Manual De Usuario

Descargar
Página de 372
LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
172
 
Manual, 04/2011, A5E03556174-01 
4.4.6 
Edge triggered wiping relay 
Short description 
An input pulse generates a preset number of output pulses with a defined pulse/pause ratio 
(retriggerable), after a configured delay time has expired.      
 
Symbol in LOGO! 
Wiring 
Description 
Input Trg 
A signal at input Trg (Trigger) triggers the times for 
the edge triggered wiping relay. 
Input R 
A signal at input R resets the current time (T
a
) and 
the output. 
4
7UJ
5
3DU
 
Parameter 
The interpulse width T
L
 and the pulse width T
H
 are 
configurable. 
N determines the number of pulse/pause cycles 
TL/TH: 
 Range of values: 1...9 
Retentivity:  
/ = No retentivity 
R = The status is retentive. 
 
Output Q 
Q is set after TL has expired, and reset after TH has 
expired. 
Parameters TH and TL 
Note the information on parameter T in topic Time response (Page 151). 
The pulse width TH and the interpulse width TL can be provided by the actual value of 
another already-programmed function. You can use the actual values of the following 
functions:  
●  Analog comparator  (Page 218) (actual value Ax – Ay) 
●  Analog threshold trigger  (Page 213) (actual value Ax) 
●  Analog amplifier  (Page 226) (actual value Ax) 
●  Analog multiplexer  (Page 248) (actual value AQ) 
●  Analog ramp  (Page 251) (actual value AQ) 
●  Mathematic instruction (Page 265) (actual value AQ) 
●  PI controller  (Page 256) (actual value AQ) 
●  Up/down counter  (Page 201) (actual value Cnt) 
 
If your LOGO! is a LOGO! 0BA7, you can additionally use the actual values of the following