LOGO! functions 
 
4.4 Special functions list - SF 
LOGO! 
Manual, 04/2011, A5E03556174-01 
217
 
Timing diagram B: Function with positive difference Δ 
$[
4
2Q
2II 2Q˂
 
Functional description 
The function fetches the analog signal at input Ax.  
Ax is multiplied by the value of the A (gain) parameter, and the value at parameter B (offset) 
is added to product, i.e. (Ax • gain) + offset = actual value of Ax. 
Output Q is set or reset, depending on the set (On) threshold and difference value (Δ). The 
function automatically calculates the Off parameter: Off = On + Δ, whereby Δ may be 
positive or negative. See the calculation rule below. 
Calculation rule 
●  When you set a negative differential value Δ, the On threshold ≥ Off threshold, and: 
Q = 1, if the actual value Ax > On 
Q = 0, if the actual value Ax ≤ Off.  
See the timing diagram A. 
●  When you set a positive differential value Δ, the On threshold < the Off threshold, and Q 
= 1, if: 
On ≤ actual value Ax < Off. 
See the timing diagram B. 
Setting the Par parameter 
The gain and offset parameters are used to adapt the sensors to the relevant application. 
View in programming mode (example): 
2Q
%
3DUDPHWHUSURWHFWLRQPRGH
'LIIHUHQWLDOYDOXHIRUWKHRQRII
WKUHVKROG
2QRIIWKUHVKROG
 
Press   
S
%
$
%
'HFLPDOVLQWKHPHVVDJHWH[W
2IIVHW
*DLQ