LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
252
 
Manual, 04/2011, A5E03556174-01 
Symbol in LOGO! 
Wiring 
Description 
Parameter 
Level 1 and Level 2:  
Levels to be reached 
Range of values for each level:  
-10,000 to +20,000 
MaxL: 
Maximum value that must not be exceeded under any 
circumstances. 
Range of values: -10,000 to +20,000 
StSp: 
Start/Stop offset:: value that is added to Offset "B" to 
create the start/stop level. If the Start/Stop offset is 0, 
then the start/stop level is Offset "B".. 
 Range of values:  
 0 to +20,000 
Rate: 
Acceleration with which level 1, level 2 or Offset is 
reached. Steps/seconds are issued. 
 Range of values:  
 1 to 10,000 
A: Gain 
 Range of values:  
 0 to 10.00 
B: Offset 
 Range of values:  
 ±10,000 
p: Number of decimals 
 Range of values: 
 0, 1, 2, 3 
Output AQ 
The output AQ is scaled using the formula:  
Range of values for AQ: 
0 to +32767 
(Current Level - Offset "B") / Gain "A" 
Range of values: 
0 to +32767 
Note: 
When AQ is displayed in parameter mode or 
message mode, it is displayed as an unscaled value 
(engineering units: current level).