Siemens 6ED1050-1AA00-0BE8 Manual De Usuario
Technical data
A.1 General technical data
LOGO!
320
Manual, 04/2011, A5E03556174-01
Criterion
Tested in accordance with
Values
Ambient mechanical conditions
Degree of protection
Degree of protection
IP 20 for LOGO! Base Modules,
expansion modules, and the
LOGO! TD excluding the TD
front panel
IP 65 for LOGO! TD front panel
IP 65 for LOGO! TD front panel
Vibrations:
IEC 60068-2-6
5 ... 8.4 Hz
(constant amplitude 3.5 mm)
8.4 ... 150 Hz
8.4 ... 150 Hz
(constant acceleration 1 g)
Shock
IEC 60068-2-27
18 shocks
(half-sine wave 15g/11 ms)
Free fall (packaged)
IEC 60068-2-32
0.3 m
Electromagnetic compatibility (EMC)
Noise emission
Noise emission
EN 55011/A
EN 55022/B
EN 50081-1
EN 50081-1
(domestic area)
Limit class B group 1
Electrostatic discharge
IEC 61000-4-2
Severity 3
Severity 3
8 kV air discharge
6 kV contact discharge
6 kV contact discharge
Electromagnetic fields
IEC 61000-4-3
Field strength 1 V/m and 10
V/m
HF currents on cables and cable
shielding
IEC 61000-4-6
10 V
Burst pulses
IEC 61000-4-4Severity 3
2 kV (supply and signal lines)
High-energy surge pulse (applies only
to LOGO! 230 ...)
IEC 61000-4-5Severity 3
1 kV (power lines) symmetrical
2 kV (power lines) asymmetrical
2 kV (power lines) asymmetrical
Safety to IEC
Clearance and creepage distance
Clearance and creepage distance
rating
IEC 60664, IEC 61131-2,
EN 50178
cULus to UL 508, CSA
C22.2 No. 142
With LOGO! 230 R/RC,
also IEC60730-1
Fulfilled
Insulation strength
IEC 61131-2
Fulfilled
Cycle time
Cycle time per function
Cycle time per function
< 0.1 ms
Startup
Startup time at power-up
Startup time at power-up
typ. 9 s