Technical data 
 
A.7 Technical data: LOGO! DM8 24R and LOGO! DM16 24R 
LOGO! 
Manual, 04/2011, A5E03556174-01 
333
 
 
LOGO! DM8 24R 
LOGO! DM16 24R 
Continuous current I
th
 
max. 5 A per relay 
max. 5 A per relay 
Surge current 
max. 30 A 
max. 30 A 
Incandescent lamp load (25000 
switching cycles) at 
1000 W 
1000 W 
Fluorescent tubes with ballast 
(25000 switching cycles) 
10 x 58 W 
10 x 58 W 
Fluorescent tubes, 
conventionally compensated 
(25000 switching cycles) 
1 x 58 W 
1 x 58 W 
Fluorescent tubes, 
uncompensated (25000 
switching cycles) 
10 x 58 W 
10 x 58 W 
Derating 
none; across the entire 
temperature range 
none; across the entire 
temperature range 
Short circuit-proof cos 1  
Power protection B16, 600A 
Power protection B16, 600A 
Short circuit-proof cos 0.5 to 0.7  Power protection B16, 900A 
Power protection B16, 900A 
Parallel output circuits for power 
increase 
Not permitted 
Not permitted 
Protection of output relay (if 
desired) 
max. 16 A, 
characteristic B16 
max. 16 A, 
characteristic B16 
Switching rate  
Mechanical 
10 Hz 
10 Hz 
Ohmic load/lamp load 
2 Hz 
2 Hz 
Inductive load 
0.5 Hz 
0.5 Hz 
Notice: For fluorescent lamps with capacitors, the technical data of fluorescent lamp ballasts 
must also be considered. If the maximum allowed surge current is exceeded, fluorescent 
lamps must be switched with appropriate contactor relays.  
The data was determined with the following devices: 
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 uncompensated. 
Siemens fluorescent tubes 58W VVG 5LZ 583 3-1 parallel compensated with 7μF. 
Siemens fluorescent tubes 58W VVG 5LZ 501 1-1N with ballast.