LOGO! installation and wiring 
 
2.4 Putting into operation 
 
LOGO! 
68
 
Manual, 04/2011, A5E03556174-01 
CM AS Interface, communication states 
The CM AS Interface has three communication states: The LED is lit green, red or flashes 
red/yellow.   
 
LED AS-I is lit 
Green 
Red 
Red/Yellow 
AS Interface communication OK  AS Interface communication 
failed 
Slave has address "0". 
CM AS Interface, behavior on communication failure   
●  If the AS Interface voltage fails, communication between the LOGO! system and the 
expansion modules, which are arranged to the right of the LOGO! CM AS Interface 
expansion module, is interrupted. 
Recommendation: Position LOGO! CM AS Interface on the far right side. 
●  If communication is interrupted, the switching outputs are reset after about 40 to 100 ms. 
CM EIB/KNX, communication states   
The CM EIB/KNX has three communication states: The LED is lit green, red or orange. 
 
LED BUS is lit 
Green 
Red 
Orange 
Bus connection OK, 
communication OK, 
no programming mode 
Bus connection interrupted 
Programming mode active and 
bus connection OK 
CM EIB/KNX, behavior on communication failure 
   
●  LOGO! voltage failure 
If there is a power failure of LOGO! or a disruption in the communication to the LOGO! 
master or to the communication partner on the left side, the outputs are set to 0. The 
RUN/STOP LED lights up red after a second. 
●  LOGO! voltage recovery 
LOGO! starts up again, CM EIB/KNX sends the parameterized states. 
●  CM EIB/KNX voltage failure 
All the inputs of the LOGO! master on the 
EIB
 are set to 0 by the LOGO! master. 
●  CM EIB/KNX voltage recovery 
All the outputs of the LOGO! master on the 
EIB
 are updated. The inputs are read by the 
EIB
 depending on the parameterization. 
●  Short circuit on the bus or bus interruption 
The behavior can be parameterized in the LOGO! configuration window of the application 
program in ETS (EIB Tool Software). The red light is set after 5 seconds. 
●  Bus recovery 
The behavior can be parameterized in the LOGO! configuration window.