4.5.6 Watchdog 
Registers 
The watchdog registers are 32 bits in width. For read/write access of the watchdog registers to be meaningful, a 32-bit 
access is required. However, a byte-by-byte write operation is not intercepted by the hardware. 
To prevent the watchdog registers from being written to inadvertently, e.g., in the event of an undefined computer crash, 
the writable watchdog registers are provided with write protection. The upper 16 bits of the registers are so-called key 
bits. In order to write a valid value in the lower 16 bits, the key bits must be set to 0x 9876 yyyy (yyyy is the 16-bit value 
to be written). 
4.5.7 
Address Assignment of Watchdog Registers 
Watchdog  
(Base Address 0x4000_2100)
 
Register Name 
Offset Address
 
Address Area
Access
 
Default
 
Description
 
CTRL/STATUS
 
0x0000  
4 bytes 
R/W 
0x00000000
Control/status register WD 
RELD0_LOW 
0x0004 
4 bytes 
R/W 
0x0000FFFF
Reload register 0_Low Bits 0-15 
RELD0_HIGH 
0x0008 
4 bytes 
R/W 
0x0000FFFF
Reload register 0_High Bits 16-31
RELD1_LOW 
0x000C 
4 bytes 
R/W 
0x0000FFFF
Reload register 1_Low Bits 4-19 
RELD1_HIGH 
0x0010 
4 bytes 
R/W 
0x0000FFFF
Reload register 1_High Bits 20-35
WDOG0 
0x0014 
4 bytes 
0xFFFFFFFF
Watchdog timer 0 value register 
WDOG1 
0x0018 
4 bytes 
0xFFFFFFFF
Watchdog timer 1 value register 
Table 12: Overview of WD Registers 
4.5.8 Watchdog 
Register 
Description 
 
CTRL/STATUS  
 
 
R/W           
Addr.: 0x4000_2100        Default: 0x0000_0000 
Description Control/status 
register Configuration and control bits for the watchdog. 
 
Bit No. 
Name 
Description 
Run/xStop_V0 
Enable/disable watchdog counter 0: 
0: Watchdog counter 0 disabled 
1: Watchdog counter 0 enabled 
Note: If this bit = 0, the WDOUT0_n output of the ERTEC 200 is active (0), 
the interrupt of the watchdog (WDINT) is “0”, and the status bit of counter 0 
(Bit 3) is “0”. 
Run/xStop_Z1 
Enable/disable watchdog counter 1: 
0: Watchdog counter 1 disabled 
1: Watchdog counter 1 enabled 
Note: If this bit = 0, the WDOUT1_N output of the ERTEC 200 is passive (1) 
and the status bit of counter 1 (Bit 4) is “0”. 
Load(Trigger) 
Watchdog trigger (load watchdog counters 0 and 1 with the value of the 
 effect at the instant of writing. 
the watchdog counter; a 
unters. 
reload registers): 
0: Do not trigger watchdog 
1: Trigger watchdog 
While this bit can be read back, it only has an
Writing a value of 1 to this bit is sufficient to trigger 
0/1 edge is not needed. 
The trigger signal acts on both watchdog co
Status_Counter 0 
Watchdog status counter 0 (writing is ignored): 
0: Watchdog counter 0 has not expired 
1: Watchdog counter 0 has expired 
Note: This bit can only be read as ‘1’ if Run/xStop_Z0 is active (1). 
Status_Counter 1 
Watchdog status counter 1 (writing is ignored): 
0: Watchdog counter 1 has not expired 
1: Watchdog counter 1 has expired 
Note: This bit can only be read as ‘1’ if Run/xStop_Z1 is active (1).  
15-5 
Reserved 
Not relevant (read=0) 
31-16 
Key bits 
Key bits for writing to this register (read=0). 
If bits 31-16=9876h, writing of bits 0-4 of this register has an effect; 
otherwise, no effect. 
 
 