Configuration / diagnostics using remote mechanisms 
 
6.3 Configuration using Web Based Management (WBM) and Command Line Interface (CLI) 
 
SCALANCE X-200 
226
 
Operating Instructions, 12/2011, A5E00349864-19 
Yellow: 
If the link power margin enters this range, maintenance is necessary. The boundary of the 
yellow area is at a link power margin of 2 dB. To ensure long-term functionality of the 
system, the maintenance should be performed. If the link power margin is in the yellow 
range, this is signaled by the FO LED lighting up. 
 
NOTICE 
 
The page for diagnostics of fiber-optic cable only shows correct link power margins when 
plastic optical fiber (POF) is used. If polymer cladded fiber (PCF) is used, diagnostics is not 
possible. 
 
6.3.5.35 
The "Loop Detection Config" WBM menu 
Loop Detection Configuration 
On this page, you specify for the ports for which loop detection will be activated. These ports 
send test frames. If these frames are sent back to the device, there is a Loop. 
 
 
Note 
Note that the functions of the "Loop Detection Configuration" WBM menu are not available 
for X200IRT. 
 
If the frames are received again at another port of the same device, there is a "Local Loop" 
involving this device. 
If the sent frames are received again at the same port, there is a "Remote Loop" involving 
other network components. 
 
 
Note 
Note that loop detection is only possible at ports that were not configured as ring ports.