These instructions apply to the field 
installation of end switch kits on Greenheck 
model WD Backdraft Dampers. These end 
switch kits can be used in conjunction 
with MP-100, MP-200, and MP-300 Series 
actuators.
End switches are typically wired to a fan 
and/or to a light serving as an open/not open 
indicator. When the damper is powered open, 
one of the damper blades makes contact with 
the spring rod of the end switch which in turn 
makes a connection allowing power to flow to 
the fan and/or light. This set up would be used 
when it is desirable to ensure that the damper 
is fully open before the fan starts.
Instructions:
1.  Position end switch such that the back side of damper blade trips 
the spring rod.
2.  Mount end switch bracket to damper frame or ductwork using 
#10 x 
1
2
 in. self-drilling sheet metal screws
Damper Frame
1
2
 in.-14 NPSM
Damper
Blade
Damper
Tie Bar
Damper Frame
1
2
 in.-14 NPSM
Damper
Blade
Damper
Tie Bar
Spring Rod
Spring Rod
2
3
3
4
1
2
3
3
4
1
End Switch Installation On 
WD-100 Series Dampers
Damper Frame
1
2
 in.-14 NPSM
Damper
Blade
Damper
Tie Bar
Damper Frame
1
2
 in.-14 NPSM
Damper
Blade
Damper
Tie Bar
Spring Rod
Spring Rod
2
3
3
4
1
2
3
3
4
1
End Switch Installation On 
WD-200 & 300 Series Dampers
Part Number 452723
End Switch Kit
For use on WD series Dampers
Part # Qty.
Description
1
1
End switch mounting bracket
2
1
End switch 
   UL/CSA Rating L67
   15 Amps:   125, 250, or 480 VAC
0.25 Amps:   250 VDC
0.50 Amps:   125 VDC
3
2
#6-32NC x 11/2 in. machine screws with 
nuts (packaged in end switch housing)
4
2
#10 x 1/2 in. self-drilling sheet metal 
screws
Field Installation Instructions
Copyright © 2008 Greenheck Fan Corporation 
#452723 End Switch Rev 3 Aug 2008
Common
L1
Wiring Illustration
End
Switch
M
Green
Fan or
Light
N.C.
N.O.
L2
Damper
Actuator
Wiring Illustration
Note: Some actuators are multi-tap, use correct connections per 
actuator wiring diagram.