Introduction
 
MPC Level 
V 1.0, Beitrags-ID: 42200753 
11
 
C
opyr
ight 
 Si
em
ens
 AG 2
010
 Al
l r
ights r
es
er
ved 
2.3.3 
Position Control 
The control loop shows integrating behaviour if the position of mechanical parts is 
controlled and the speed of the actuator is available as manipulated variable. An 
"equilibrium condition" without move in the position only exists for a speed equal to 
zero. The valve actuator is a common example for position control in process 
plants. However, the valve position controllers are mostly integrated in the corre-
sponding actuators and hence not an issue for the DCS. 
 
2.3.4 
Example of Multivariable Control with Integral Part Transfer Function 
The level of most chemical reactors has to be kept in certain limits during continu-
ous operation. Therefore the drain flow (rotational speed of pump or set point of 
subordinated flow controller) is available as manipulated variable and results in an 
integral part transfer function as described in section 2.3.1. A multivariable control 
problem including integral part transfer functions results if an additional quality con-
trol exists at the same reactor, e.g. with the reactor pressure as manipulated vari-
able (set point for the slave pressure controller). The residence time of the fluid in 
the reactor as well as the progress and the result of the reaction (the product qual-
ity) are dependant on the drain flow, which is the manipulated variable of the level 
controller.