Introduction
Thank you for choosing the Siemens TPSA9040 Residential
Transient Voltage Surge Suppressor.
Save this manual!  It includes instructions for obtaining
warranty service and for returning a defective device.
Please read and understand all information in this manual
prior to installation.  The procedures contained herein are
not intended to supersede local or national electrical
codes.  Check all applicable electrical codes to ensure
compliance.
  In all instances, local and national electrical
code requirements are to be followed.
This manual provides instructions for installing the
TPSA9040 Transient Voltage Surge Suppressor (TVSS). The
TPSA9040 TVSS (Figure 1) can be mounted three ways.  The
preferred way is to mount the TVSS directly to the outside of
the electrical panel equipment using the chase nipple on
the body of the TVSS.  It can also be installed against a
panel/wall using installer supplied hardware, or it can be
installed using an optional Flush Mount Kit. The latter two
methods require use of additional conduit and hardware
(not provided).
The TPSA9040 provides a broad range of protection from
damaging transient voltage surges and spikes. Proper
installation is imperative to maximize the effectiveness and
overall performance of this device. This device must be
installed by a licensed electrician.
  The electrician should
follow the steps outlined in this manual to insure proper
installation.
Note: Siemens products are extensively tested to industry
standards as set by IEEE C62.41 and C62.45, for Categories
A, B, and C.  The TPSA9040 is listed to the most recent
edition of UL 1449.  This product is suitable for installation
on electrical distribution equipment capable of delivering
not more than 25,000 rms symmetrical amperes.
During installation into an electrical system, the TPSA9040
must NOT be energized until the electrical system is
installed, inspected and tested.  All conductors must be
connected and functional, including neutral (if required).
Failure to follow the guidelines in this manual can lead
to abnormally high voltage being applied to the TVSS. This
may cause the TPSA9040 unit to become inoperative. The
warranty does not cover an incorrectly installed device.
Do not high potential test the electrical system with the
TVSS connected. 
Failure to disconnect the TVSS during
elevated voltage testing will result in damage to the
suppression components and/or other electronic compo-
nents (see Safety Information).
Parts List and Inspection
Items included in the package consist of the following:
1 TPSA9040 Transient Voltage Surge Suppressor
1 User’s Manual (this document)
If the Flush Mount Kit (Part #KITFMC) was ordered, additional
parts are supplied as follows:
1 Flush Mount Panel
1 Flush Mount Installation Instructions
4 Pan-head Screws
Carefully inspect each item in the package for signs of
damage. If damage is found, please contact Siemens
Technical Support: 1-888-333-3545. For more information
about this product or other Siemens products, visit
www.sea.siemens.com.
Safety Information
This section provides pertinent safety information that must
be considered before installing the TVSS.
Do not install this device during a lightning storm.
This device is rated NEMA 4X. Suitable for indoor
and outdoor applications. The conduit nipple must be
sealed against the panel using watertight fittings (not
supplied) to ensure a watertight connection.
Do not install the surge protector in an excessively
hot or moist location.
Other safety considerations are listed on the
following page.