Ventless Hood System 
 
Installation 
 
 
15 
Fire Extinguishing System 
 
 
In the event of an appliance fire, serious injury, property damage or death could 
occur if any part of the appliance obstructs the spray nozzles. Ensure that lids 
and/or other parts of the appliance do not obstruct the spray pattern of either 
nozzle.  
 
 
The fire extinguishing system components used in this hood have been evaluated 
by U.L. in the course of their classification for use on this hood. 
 
An authorized Range Guard
® distributor must install and activate the filter hood 
fire extinguishing system. To locate an authorized Range Guard
® Distributor use 
the following contact information:  
 
Ronald Woodward 
Technical Service Specialist 
Badger Fire Protection 
4251 Seminole Trail 
Charlottesville Va. 22911 
Office: 800-446-3857 ext. 111 
Fax: 434-974-4113 
Mobile: 434-981-0505 
 
1.  After the hood has been properly secured to prevent movement, locate the end-of-line remote pull 
station (at a point of egress or exit) in a manner approved by the local authority and in 
accordance with applicable codes. To install the end-of-line remote, use ½” EMT and Range 
Guard
® corner pulleys #97915.  
 
2.  Install two UL Listed; type “A”, 165
° F. fusible links (load rating 3-45 lbs.) in the two appliance 
detector positions (one in front of the grease baffle, one behind the grease baffle). 
 
 
FUSIBLE 
LINKS