Greenheck Fan FSD-311V Manual De Usuario

Descargar
Página de 6
APPLICATION
Model FSD-311V is a vertical blade class I leakage rated combi-
nation fire smoke damper. High strength airfoil blades ensure the 
lowest resistance to airflow in HVAC systems with velocities to 4000 
fpm (20.3m/s) and 4 in. wg (1.0 kPa).
RATINgs
UL 555 Fire Resistance Rating:  
 
Fire Rating: 
1½ hours 
 
Dynamic Closure Rating: Actual ratings are size dependent 
 
Max. Velocity: 
up to 4000 fpm (20.3 m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa)
UL555S Leakage Rating: 
 
Leakage Class: 
 
Operational Rating: 
Actual ratings are size dependent 
 
Max. Velocity: 
up to 4000 fpm (20.3m/s) 
 
Max. Pressure: 
4 in. wg (1 kPa) 
 
Maximum Temperature:  350°F (177°C)- depending upon  
 
 
the actuator
sTANdARd CONsTRuCTION
 
Frame:  
5 in. x 1 in. (127mm x 25mm) 
 
 
galvanized steel hat channel with 
 
 
reinforced corners. A low profile 
 
 
head and sill are used on sizes less 
 
 
than 17 in. (432mm) high to 
 
 
maximize free area and  
 
 
performance. 
 
Blades:  
Double skin airfoil shape of 
 
 
galvanized steel with full length 
 
 
structural reinforcement. 14 ga.  
 
 
(2 mm) equivalent thickness.  
 
seals: 
Extruded silicone rubber blade 
 
 
seals. Flexible stainless steel jamb 
 
 
seals. 
 
Closure device: 
RRL 165°F (74°C) 
 
Linkage: 
Concealed in jamb. 
 
Axles: 
1
/
2
 in. (13mm) dia. plated steel. 
 
Bearings: 
304 stainless steel
sIze LImITATIONs:
 
 
minimum size: 
6 in. W x 8 in. H 
 
 
(152mm  W x 203mm H) 
 
maximum size-  
 
Single Section:  
50 in. W x 32 in. H 
 
 
(1270mm W x 813mm H) 
 
Multiple Section: 
100 in. W x 32 in. H 
 
 
(2540mm W x 813mm H)
OPTIONAL FeATuRes
• OCI (Open closed indication switches) 
• Electric or pneumatic actuators to accomplish smoke 
  management and system functions. 
• Transitions (R, C, O) 
• POC retaining angles 
• Momentary Switch 
• Sealed transitions and sleeves 
• RRL/OCI (Open closed indication switches) 
• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's  
  available 
• TOR (remote override closure allows damper to perform smoke 
  management functions during a fire emergency.) 
• PRV (pneumatic relief valve) 
• Security Bars 
• Sealed transitions and sleeves 
model Fsd-311V
Combination
 FIRe smOKe dAmPeRs
Steel Airfoil Blades
UL 555S Leakage Class I 
UL555 1 1/2 Hour Fire Resistance Rating
*W&H dimensions furnished approximately 
1
/
4
 in. (6mm) undersize.
W*
H*
Model FSD-311V meets the requirements for fire 
dampers, smoke dampers and combination fire 
smoke dampers established by:
National Fire Protection Association 
    NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC  International Building Codes
ICBO  uniform Building Codes 
CsFm California state Fire marshal
  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
“uL CLAssIFIed (see complete marking on 
product)”
“uL CLAssIFIed to Canadian safety standards 
(see complete marking on product)”
 
Standard 555 & 555S (Listing #R13317)
Installation instructions available at www.greenheck.com