Greenheck Fan 35 Prospecto

Descargar
Página de 1
Application and Design
Ductmate
®
  is  used  to  connect  a  damper  sleeve  to 
a  rectangular  duct  when  a  tight  duct  connection  is 
required.  The  Ductmate  connector  gives  a  nearly 
airtight cross connection without the use of slip joints, 
and  is  an  acceptable  breakaway  connection  when 
installed properly.
Particular  attention  should  be  given  to  the  length  of 
the  sleeve  extending  beyond  the  wall  or  floor.  The 
determining  factor  is  dependent  on  whether  or  not 
there  is  an  actuator  and/or  access  door.  If  there  is 
no actuator and/or factory mounted access door, the 
maximum is 6 inches (152mm) extending beyond the 
wall or floor. If there is an actuator or factory access 
door on the side of the wall, the maximum is 16 inches 
(406mm).
Versa-cleats  are  available  in  packages  of  10,  25,  or 
50.  See  installation  instructions  for  spacing  of  cleats 
(468502 Quick Connect Breakaway Supplement). 
Standard Construction
         Flange:  20 ga. (1mm) galvanized 
Corner Clips:  Galvanized
        Gasket:  Extruded butyl for use between mating  
                        flanges (not supplied by Greenheck)
        Sleeve:  Maximum thickness - 16 ga. (1.5mm)                 
                       galvanized steel
Mounting Options
    
One side:  Actuator side (FSD/SMD series) 
                        K side (DFD/FD series)
   Both Sides:  Actuator or K side attached/ Opposite side 
                       unattached or both sides mechanically  
 
fastened
Size Limitations
FSD/SMD series:  Minimum damper size is 8 in. W x 6 in. H  
                              (203mm x 152mm) Maximum width is  
                              based on model limitations. Maximum                
                              height is limited to 84 inches (2133mm). 
   FD/DFD series:  Minimum damper size is 6in. W x 6 in. H  
                              (152mm x 152mm) Maximum width and  
                              height is based on model limitiations.
DUCTMATE
®
 35
Copyright © 2007 Greenheck Fan Corporation
Ductmate® 35 Rev. 4 May 2007
Screw Spacing Schedule (per Ductmate instructions)
Duct wall size 
inches (mm)
0-4 in. wg
(0 - 1 kPa)
6 in. wg
(1.5 kPa)
0-24
(0 - 610)
1 screw each corner
1 screw each corner
25-48
(635 - 1219)
1 screw each corner 
plus 1 @ center
1 screw each corner 
plus 1 @ center
49 and over
(1245 and over)
1 screw each corner 
plus 1 screw each 
24 inches (610mm)
2 screws each 
corner plus 1 screw 
each 24 inches 
(610mm)