Greenheck Fan 471837 Prospecto

Descargar
Página de 2
Part Number 471837
Installation Instructions
for TOR 
(Temperature Limited 
Override)
 on FSD, SEFSD, 
SSFSD series
Steps to install an TOR in a Fire Smoke Damper:
Upturned Leg Faces
Away From Blade End
#10 x 1/2 in. Tek Screw
or Equivelant
Part  No. 415555
2 Req’d
0.166 in. dia.
2 Places
Indicator Bracket
Part No. 658594
1 Req’d
#10 x 1/2 in. Tek
Screw
or Equivelant
Part  No. 415555
2 Req’d
Upturned Leg
Faces Away From
Blade End
Indicator Bracket
Part No. 658594
1 Req’d
1.625
1.750
Indicator Link
(short or long; see C)
1 Req’d
Push Nuts
2 Req’d
Gasket
1 Req’d
J-Box Cover
1 Req’d
#10-16 x 3/4 in
.
SIHWH Screw
2 Req’d
J-Box
1 Req’d
A
B
C
D
TOR
1 Req’d
Note: Indicator Link Part Nos
.
For Standard Sleeve (short): 457808
For Extended Sleeve (long): 457801
TOR - Exploded View
Airfoil Blade
3-V Blade
Indicator
Bracket
Indicator
Link
1)  Drill/saw a 3
5⁄8
 in. (92mm) diameter hole in sleeve 
(Detail 2).
2)   Attach indicator bracket to blade. For an airfoil 
blade dampers, use existing holes in blade (Detail 
1-A). For a 3V blade damper, drill two 0.166 
in. (4mm) holes (Detail 1-B). Fasten bracket to 
bladewith #10 x 1/2 in. (13mm) TEK screws (or 
equilavent).
3) Fit indicator link into blade bracket (Detail 1-C).
4)  Insert TOR unit through hoel in sleeve (round end 
inside). 
5)  Place 4 in. x 4 in. J-box over the flange of the TOR 
unit and align holes.
6)  Mount control box to sleeve/sideplate with  
#10-16 x3/4 in. (19mm) TEK screw or equilavent 
(Detail 1-D).
7)  Place one pushnut on the switch wire. Place 
indicator link on switch wire and secure with a 
second pushnut (Detail 1-D).
8) Complete wiring and install J-box cover.
Detail 1