Check Pumpout System Controls and Optional Pumpout Compressor 
Controls include an on/off switch, a 3-amp fuse, the compressor overloads, an internal 
thermostat, a compressor contactor, and a refrigerant high pressure cutout. The high pressure 
cutout is factory set to open at 161 psig (1110 kPa) and reset at 130 psig (896 kPa). Check that 
the water-cooled condenser has been connected. Loosen the compressor holddown bolts to 
allow free spring travel. Open the compressor suction and discharge service valves. Check that 
oil is visible in the compressor sight glass. Add oil if necessary. 
 and 
 
sections for details on transfer of refrigerant, oil specifications, etc.
High Altitude Locations
Recalibration of the pressure transducers will be necessary as the machine was initially 
calibrated at sea level. Please see the calibration procedure in the 
 
section.