Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
Notes on Module Operation 
1. The machine operator monitors and modifies configurations in the microprocessor through 
the 4 softkeys and the LID. Communication with the LID and the PSIO is accomplished 
through the CCN bus. The communication between the PSIO, SMM, and both 8-input 
modules is accomplished through the sensor bus, which is a 3-wire cable. 
On sensor bus terminal strips, Terminal 1 of PSIO module is connected to Terminal 1 of 
each of the other modules. Terminals 2 and 3 are connected in the same manner. See   
, and 
. If a Terminal 2 wire is connected 
to Terminal 1, the system does not work. 
2. If a green LED is solid on, check communication wiring. If a green LED is off, check the red 
LED operation. If the red LED is normal, check the module address switches (
, an
). Proper addresses are:
Module
Address
SW1
SW2
SMM (Starter Management Module)
8-input Options Module 1
8-input Options Module 2
3
6
7
2
4
2