Carrier 17/19EX Manual De Usuario

Descargar
Página de 437
Alarms and Alerts 
Alarm (*) and alert (!) status are indicated on the Default screen and the Status tables. An 
alarm (*) will shut down the compressor. An alert (!) notifies the operator that an unusual 
condition has occurred. The machine will continue to operate when an alert is shown. 
Alarms are indicated when the control center alarm light (!) flashes. The primary alarm 
message is viewed on the default screen and an additional, secondary, message and 
troubleshooting information are sent to the Alarm History table.
Note: When an alarm is detected, the LID default screen will freeze (stop updating) at the time 
of alarm. The freeze enables the operator to view the machine conditions at the time of 
alarm. The Status tables will show the updated information. Once all alarms have been 
cleared (by pressing the RESET softkey), the default LID screen will return to normal 
operation.