Deadband
This is the tolerance on the chilled water/ brine temperature 
CONTROL POINT. If the water 
temperature goes outside of the 
DEADBAND, the PIC opens or closes the guide vanes in 
response until it is within tolerance. The PIC may be configured with a 0.5° to 2° F (0.3° to 
1.1° C) deadband. 
DEADBAND may be viewed or modified on the Equipment Service1 table. 
For example, a 1° F (0.6° C) deadband setting controls the water temperature within ±0.5° F 
(0.3° C) of the control point. This may cause frequent guide vane movement if the chilled water 
load fluctuates frequently. A value of 1° F (0.6° C) is the default setting. 
Proportional Bands and Gain
Proportional band is the rate at which the guide vane position is corrected in proportion to 
how far the chilled water/brine temperature is from the control point. Proportional gain 
determines how quickly the guide vanes react to how quickly the temperature is moving from 
CONTROL POINT.
The Proportional Band can be viewed/modified on the LID. There are two response modes, 
one for temperature response above the control point, the other for response below the control 
point. 
The first type is called 
PROPORTIONAL INC BAND, and it can slow or quicken vane 
response to chilled water/brine temperature above 
DEADBAND. It can be adjusted from a 
setting of 2 to 10; the default setting is 6.5. 
PROPORTIONAL DEC BAND can slow or quicken