Condenser Pump Control 
The machine will monitor the 
CONDENSER PRESSURE and may turn on this pump if the 
pressure becomes too high whenever the compressor is shut down. 
CONDENSER 
PRESSURE OVERRIDE is used to determine this pressure point. This value is found on the 
Equipment Service1 LID table and has a default value (
). If the 
CONDENSER 
PRESSURE is greater than or equal to the CONDENSER PRESSURE OVERRIDE, and the 
ENTERING CONDENSER WATER TEMP (Temperature) is less than 115 F (46 C), then the 
condenser pump will energize to try to decrease the pressure. The pump will turn off when the 
condenser pressure is less than the pressure override less 5 psi (34 kPa), or the 
CONDENSER 
REFRIG (Refrigerant) TEMP is within 3° F (2° C) of the ENTERING CONDENSER WATER 
temperature.
Condenser Freeze Prevention
This control algorithm helps prevent condenser tube freeze-up by energizing the condenser 
pump relay. If the pump is controlled by the PIC, starting the pump will help prevent the water in 
the condenser from freezing. Condenser freeze prevention can occur whenever the machine is 
not running except when it is either actively in pumpdown or in Pumpdown Lockout with the 
freeze prevention disabled (refer to Control Test table, Pumpdown/Terminate Lockout tables).
When the 
CONDENSER REFRIG TEMP is less than or equal to the CONDENSER FREEZE 
POINT, or the ENTERING CONDENSER WATER temperature is less than or equal to the