Startup 
24
312765B
Startup
Prepare for Generator Startup
1.
Ensure main breaker for the generator is in the OFF 
position. The main breaker is the only breaker 
located in the generator room.
2.
Turn Shore/Generator Power Switch (AF) to the 
“GEN” position. 
3.
With trailer level, check fuel, oil, and coolant fluid 
levels on generator. 
4.
Check oil in compressor. 
5.
Check oil level in lube cup on air regulators assem-
bly.
6.
Close water bleed valve on compressor.
7.
Ensure proportioner is turned off. 
Start Generator
NOTE: Refer to generator operator’s manual for cold 
weather startup instructions.
8.
Press and hold bypass button.
9.
Turn ignition switch to start position until engine 
starts.
10. Release ignition switch and bypass button.
11. Wait at least five minutes after starting generator for 
readout on digital voltage/amp meter in main room 
to stabilize. 
See startup instructions and related warnings in 
supplied manuals. See Related Manuals on page 3.
NOTICE
To prevent damage to spray machine and generator, 
do not run generator out of fuel. Follow shut down 
procedure on page 28 when fuel level is getting low.
F
IG
. 14: Generator Bypass Button
TI12894a1