Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, 
use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft 
bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such 
as dust.
Dampers and their electric/pneumatic actuator(s) must be maintained, cycled, and tested in accordance with:
•  The latest editions of NFPA 80, 90A, 92A, UL864, and local codes.
•  Actuator manufacturer recommendations.
Copyright © 2006 Greenheck Fan Corporation
461868 FSDR-XXX Rev. 7  March 2006
 Symptom 
          Possible Cause 
        Corrective Action  
 
 
Frame is out of round causing  
Adjust frame such that it is round
 
 
blades to bind on jamb seals 
   
 
 
Actuator linkage loose 
Close damper, disconnect power, adjust  
 
 
 
and tighten linkage
 
 
Defective motor 
Replace
 
 
Screws in damper linkage 
Locate screws and remove
 
 
Actuator linkage hitting wall or floor 
Damper installed too far into wall. Move
 
 
 
out to line designated on damper label.
 
 
Contaminants on damper 
Clean with a non-oil-based solvent
 
 
 
(see Damper Maintenance)
Damper does not 
fully open and/or 
fully close
Damper does not
operate
Actuator runs hot or 
makes a humming 
noise
Link separated
Heat
Replace link
Actuator prohibited from reaching 
end of stroke
Disconnect linkage from jackshaft, 
open damper, power actuator to end of 
spring, tighten linkage. Verify amp draw.
RRL, or TOR sensor 
tripped
Heat 
No power supplied to the actuator
Push reset button located on backside 
of RRL or TOR.
Damper trouble Shooting
The following is a possible cause and correction list for common concerns with the dampers.
Round duct connections to shall be attached with #8 sheet metal screws as follows:
  • Ducts 22 in. dia. and smaller shall have three screws.
  • Ducts larger than 22 in. dia. up to and including 24 in. dia. shall have five screws.
NOtE: All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by 
Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, or Grey Pookie applied in accordance 
with SMACNA recommendations.
9. Round Duct Connections