CLS-EXP-DIMU 
Functional Summary 
Crestron Electronics, Inc.
 
Installation Guide – DOC. 6682B
 
15 Volvo Drive   Rockleigh, NJ 07647
 
(2020684)
   
The CLS-EXP-DIMU enables the expansion of the 
Crestron iLux™ Integrated Lighting System (CLS-C6 
series) and other Crestron lighting dimmers to allow 
dimming of both forward and reverse phase type loads. 
Supported loads include electronic low-voltage, magnetic 
low-voltage, incandescent, neon/cold cathode, or 2-wire 
dimmable fluorescent. A single model supports 120, 230, 
or 277 Volt loads up to 16 Amps. 
The CLS-EXP-DIMU simplifies installation by auto-
detecting the dimmable load type connected to it and 
selecting the appropriate dimming mode to control that 
load. Reverse phase (trailing edge) dimming supports 
incandescent and electronic low-voltage load types, while 
forward phase (leading edge) dimming handles magnetic 
low-voltage, neon, and other inductive load types. 
Any output channel of the iLux system can be used to 
control the CLS-EXP-DIMU to dim a fully loaded circuit. 
It is also compatible with CLW-Series
1
 in-wall dimmers 
and select CLX-Series lighting control modules. The 
metal enclosure is designed for mounting to a vertical 
surface and can be installed in a space used for 
environmental air as defined in NEC Article 300.22(C). 
Conduit knockouts are provided on the bottom and lower 
sides. All connections are made via screw terminals 
behind the front cover. 
•  Works with Crestron iLux (CLS-C6 series),  
DIN-1DIMU4, CLW
1
 Series, and CLX Series 
dimmers 
•  Emulates the characteristics of the dimmer that is 
controlling it 
•  Up to five Expansion Modules can be connected 
to a single dimmer output 
•  Supports 120, 230, and 277 Volt ELV, MLV, 
NCC, incandescent, and 2-wire dimmable 
fluorescent loads 
•  Auto-selects for forward or reverse phase 
•  Can be installed in an air-handling space
2
 
•  Includes threshold adjustment for setting 
minimum fluorescent dimming level 
•  Built-in air gap relay at the output 
•  Surface mount design 
1. 
CLW-Series devices must have a dedicated neutral. 
2. 
As defined in NEC Article 300.22(C). 
CLS-EXP-DIMU Physical View 
 
Specifications 
CLS-EXP-DIMU Specifications 
SPECIFICATION DETAILS 
Load Ratings 
 Output 
Channels 
 Load 
Rating 
 Minimum 
Load 
    at 120 Volts 
    at 230 Volts 
    at 277 Volts 
 Load 
Types 
 
16 Amps 
 
15 Watts 
25 Watts 
30 Watts 
Electronic Low Voltage, 
Incandescent, Neon/Cold 
Cathode, Magnetic Low Voltage, 
2-Wire Dimmable Fluorescent 
(Advance Mark 10 Powerline
®
 or 
equivalent) 
Maximum Modules per 
Dimmer Output 
Input Voltages 
 Line 
Power 
 Control 
Input 
 
120 to 277 Volts AC, 50/60 Hz 
120 or 230 Volts AC, 50/60 Hz, 
phase independent of line power 
and load, presents 25 Watts load 
to the controlling device 
Electrical Terminals 
Captive screw type; 
Accommodates two 22-12 AWG 
(0.34-4.0 mm
2
) wires 
(Continued on following page.) 
Tel: 888.CRESTRON
 
02.09
   
Fax: 201.767.7576
  
Specifications subject to 
 
www.crestron.com
 