Empire Comfort Systems DVP48FP7(0,1,2,3)(N,P)-1 Manual De Usuario

Descargar
Página de 56
Page 11
17375-10-0706
Framing and Finishing 
  1.  Choose unit location.
  2.  Frame in fireplace with a header across the top. It is important to 
allow for finished face when setting the depth of the frame.
  3.  Attach  fireplace  to  frame  using  adjustable  frame.  Preset 
depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" 
depths).
  4.  Use (8) 1/2" hex-head screws supplied in hardware package, 
to screw through slotted holes in drywall strip and then screw 
into pre-drilled holes on fireplace side. Measure from face of 
fireplace to face of drywall strip to determine final depth. 
Figure 8
Vent Pipe Clearance
Note:  Maintain one inch (1") of clearance around vertical vent 
pipe. See Fig. 9A. For horizontal vent, maintain a minimum 1" 
clearance to the bottom and sides of the vent, and 3" clearance 
to combustibles above the vent pipe. See Fig. 9B
Figure 9A
VENT PIPE
1" MINIMUM CLEARANCE AROUND VENT PIPE
Top of Vent
Combustibles NOT
allowed in shaded
area
1"
1"
3"
(25 mm)
8” Diameter
intake vent
5” Diameter flue
(25 mm)
(76 mm)
Figure 9B
INSTALLATION