176 VAC – 264 VAC ±3% 
 (Bypass) 
 
Frequency 
50 Hz / 60 Hz 
(Automatic detection) 
Frequency tolerance range 
±4 Hz  
Current consumption at full load (max.)   
PROTECT 1.M (system) 
44 A (3ph~) or 132 A (1ph~) / 155 
A (Bypass) 
PROTECT 1.040 (module) 
7.3 A (3ph~) or 22 A (1ph~) 
System disturbance factor 
λ ≥ 0.98 
UPS output 
Nominal voltage output 
220 / 230 / 240 Vac ±2% 
 (configuration via "CompuWatch" 
software) 
Nominal frequency 
50 Hz / 60 Hz ±0.2 Hz (dependent 
on mains frequency) 
Type of voltage 
Sine, distortion 
  
< 3% THD (linear load) 
  
< 6% THD (non-linear load) 
Crest factor  
3:1 
Overload behaviour 
 
Up to 105% continuous; 
with mains supply 
 
> 105% – < 130% for 30s 
  
 
 
 
130% for 2
 
Following this, automatic, 
uninterrupted switchover to 
integrated bypass (SBS).  
Switch-off after 1 min. if overload 
continues to be present (switch 
back if overload decreases = load 
< 90%) 
Overload behaviour with 
Up to 105% continuous; 
battery operation 
 
> 105% – < 130% for 30s 
  
 
 
 
130% for 2
 
Short-circuit behaviour 
3 x I
N
 for 100 ms