2.5 Power circuit wiring diagrams
Diagram for a single-unit or single modular UPS with common Mains 1 and 2
Diagram for a single-unit or single modular UPS with common Mains 1 and 2
Diagram for a frequency converter with batteries
The single-wire diagrams for typical UPS installations are given in figures 9 to 15. The heavy lines represent the cables that
must be connected
must be connected
(see the table in the previous chapter for the required cross-sectional areas of the cables).
Note:
– for frequency converters, the input and output frequencies may be different (50 or 60 Hz);
– for frequency converters, the input and output frequencies may be different (50 or 60 Hz);
– for frequency converters without batteries, ignore the battery cubicles and the + and - cables shown in the diagram.
Special case:
The UPSs can be optionally supplied with the neutral conductor not interrupted by switches Q4S, Q3BP and Q5N.
The UPSs can be optionally supplied with the neutral conductor not interrupted by switches Q4S, Q3BP and Q5N.
Fig. 9
Fig. 10
Fig. 11
mains 2
mains 1
static
switch
inverter
rectifier
charger
Q4S
Q3BP
load
battery cubicle
beside the
rectifier-inverter cubicle
earth
earth
+
-
+
-
other battery
cubicles (if
applicable)
frames interconnections for earthing
earth
QF1
Q1
Q5N
rectifier-inverter cubicle
static
switch
inverter
rectifier
charger
Q4S
Q3BP
load
battery cubicle
beside the
rectifier-inverter cubicle
earth
earth
+
-
+
-
other battery
cubicles (if
applicable)
frames interconnections for earthing
earth
QF1
Q1
Q5N
rectifier-inverter cubicle
mains 1
input
mains 2
input
mains
mains 1
inverter
rectifier
charger
load
battery cubicle
beside the
rectifier-inverter cubicle
earth
+
-
+
-
other battery
cubicles (if
applicable)
frames interconnections for earthing
earth
QF1
Q1
Q5N
rectifier-inverter cubicle
earth