Event & 
Universal
Remote
232/485
Input
Set Point
Control
Alarm
Retransmit
Comm
Input 1
Input 2
Output 1
Output 2
Output 3
Output 4
Communications
• EIA/TIA-485 or EIA/TIA-232
• Opto-isolated 
• Modbus
TM
RTU protocol
• 1200, 2400, 4800, 9600, 19200 baud rates
• 32 maximum units can be connected (With additional
485 repeater hardware, up to 247 units may be
connected)
Accuracy
• Input ranges
Type J:
0 to
750°C  or 
32 to 1382°F
Type K:
-200 to 1250°C  or 
-328 to 2282°F
Type T:
-200 to
350°C  or 
-328 to
662°F
Type N:
0 to 1250°C  or 
32 to 2282°F
Type E:
-200 to
900°C  or 
-328 to 1470°F
Type C(W5):
0 to 2315°C  or 
32 to 4200°F
Type D(W3):
0 to 2315°C  or 
32 to 4200°F
Type Pt 2:
0 to 1393°C  or 
32 to 2540°F
Type R:
0 to 1450°C  or 
32 to 2642°F
Type S:
0 to 1450°C  or 
32 to 2642°F
Type B:
870 to 1700°C
or  1598 to 3092°F
DIN:
-200 to
800°C  or 
-328 to 1472°F
JIS:
-200 to
630°C
or 
-328 to 1166°F
Process:
-1999 to 9999 units
Thermocouple Inputs
• Calibration accuracy ±0.1 percent of span ±1°C at
standard conditions
Exceptions:
Type T; 0.12 percent of span for -200°C to -50°C,
Types R and S; 0.15 percent of span for 0°C to 100°C
Types B; 0.24 percent of span for 870°C to 1700°C
• Accuracy span: 540°C/1000°F minimum
• Temperature stability: ±0.1 degree per degree change
in ambient
RTD Inputs
• Calibration accuracy ±0.1 percent of span ±1°C at
standard conditions
• Accuracy span: 540°C/1000°F minimum
• Temperature stability: ±0.05 degree per degree change
in ambient
Process Inputs
• Voltage input ranges
Accuracy ±10mV ±1 LSD at standard conditions
Temperature stability ±100ppm/°C maximum
• Milliamp input ranges
Accuracy ±20µA ±1 LSD at standard conditions
Temperature stability ±100ppm/°C maximum
Agency Approvals
• UL
®
916 file number E185611, C-UL
®
, CE, NEMA 4X
Terminals
• Touch safe
• 22 to 12 AWG     
Power 
• 100-240Vı(ac/dc) +10 percent, -15 percent; 50/60Hz,
±5 percent
• 24-28Vı(ac/dc) +10 percent, -15 percent; 50/60Hz, 
±5 percent 
• 7.0VA maximum power consumption
• Data retention upon power failure via nonvolatile
memory
Operating Environment
• 0 to 65°C, 32 to 149°F
• 0 to 90% RH, non-condensing
• Storage temperature: -40 to 85°C, -40 to 185°F 
Dimensions
• Width 52 mm (2.05 in.)
• Height 52 mm (2.05 in.)
• Length 107 mm (4.2 in.)
• Depth behind panel surface 98.4 mm (3.875 in.)
• Approximate controller weight 0.2 kg (0.4 lbs)
Modbus
TM
is a trademark of AEG Schneider Automation.
UL
®
and C-UL
®
are registered trademarks of the Underwriter’s
Laboratories, Inc.
Functionality Matrix
Allowable Operating Ranges
Note: These specifications are subject to change without prior notice.
Type J:
1.0
0
to
815°C or
32 to
1500°F
0.1
0.0
to 815.0°C or
32.0 to 999.9°F
Type K:
1.0
-270
to 1370°C or
-454 to
2500°F
0.1 -199.9
to 999.9°C or -199.9 to 999.9°F
Type T:
1.0
-270
to
400°C or
-454 to
750°F
0.1 -199.9
to 400.0°C or -199.9 to 750.0°F
Type N:
1.0
0
to 1300°C or
32 to
2372°F
0.1
0.0
to 999.9°C or
32.0 to 999.9°F
Type E:
1.0
-270
to
800°C or
-454 to
1470°F
0.1 -199.9
to 800.0°C or -199.9 to 999.9°F
Type C:
1.0
0
to 2315°C or
32 to
4200°F
0.1
0.0 to 999.9°C or
32.0 to 999.9°F
Type D:
1.0
0
to 2315°C or
32 to
4200°F
0.1
0.0
to 999.9°C or
32.0 to 999.9°F
Type Pt 2: 1.0
0
to 1395°C or
32 to
2543°F
0.1
0.0
to 999.9°C or
32.0 to 999.9°F
Type R:
1.0
0
to 1760°C or
32 to
3200°F
Type S:
1.0
0
to 1760°C or
32 to
3200°F
Type B:
1.0
0
to 1816°C or
32 to
3300°F
DIN
1.0
-200
to
800°C or
-328 to
1472°F
0.1 -199.9
to 800.0°C or -199.9 to 999.9°F
JIS
1.0
-200
to
630°C or
-328 to
1166°F
0.1 -199.9
to 630.0°C or -199.9 to 999.9°F
Process
-1999
to 9999 units