Set Up and Calibration Procedures 
Communications Set Up Group 
50 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
Revision 7 
  
 
7/08 
Communications Set Up Group 
Table 16 lists the parameters and selections available for the SET COMM group. 
Table 16 Communications Set Up Group Parameters 
Actuator Lower 
Display 
Prompt 
Selections or 
Range of Setting  
Parameter Definition/PDA HercuLink Prompt 
COMM 
 
 
DIS 
 
MODB 
 
HART 
COMMUNICATONS PARAMETERS
— Disables or enables 
parameter displays for Modbus communciations set up.  
Disabled
 Locks out access to communications displays 
and parameters. 
Modbus
— Allows access to the communication displays 
and settings for the parameters listed below.   
HART
 – selects HART as the communications protocol 
ADDRES 
1 to 99 
default = 1 
DEVICE ADDRESS
— Selects device address when used in 
a Modbus communications loop.  Select an address that is 
unique to other devices on the communications link. 
BAUD 
2400 
4800 
9600 
19.2k 
default = 19.2k 
BAUD RATE
— Selects the speed of data transfer.  All 
equipment on the link must be set to match the host setting. 
XmtDLY 
NONE 
10ms 
20ms 
30ms 
40ms 
50ms  
default = 20ms 
RESPONSE DELAY
— Selects the time delay (in 
milliseconds) before a response to a query is transmitted.  
 
DBLBYT 
 
 
 
FP   B 
FPBB 
 
FP   L 
FPLB 
default = FP B 
FLOATING POINT DATA FORMAT
— Selects the format for 
transferring floating point data.  
 
 
 
 
 
Byte Order
 
Floating Point Big Endian format
— 
    0 1 2 3 
Floating Point Big Endian format  
 
 
with byte-swapped—  
    1 0 3 2 
Floating Point Little Endian format
— 
    3 2 1 0 
Floating Point Little Endian format  
 
 
with byte-swapped—  
    2 3 0 1