This shows the latest firmware version of unit.  Press DOWN arrow to view the next statistic.
This shows the serial number of circuit board.  Press DOWN arrow to view the next statistic.
The date and time showed here is when the unit last was powered up. This can be helpful if there 
was a power outage to see how long the unit has been on. 
Check Sensors - Main Board, Flow meter, and/or Aqua-Sensor.
From the home screen, press the DOWN arrow to ADV. SETUP.  Press the CHECK MARK 
button.
Press the DOWN arrow to scroll to DIAGNOSTICS. Press the CHECK MARK button at 
DIAGNOSTICS.
Press the DOWN arrow to scroll to CHECK SENSORS. Press the CHECK MARK button at 
CHECK SENSORS.
MAIN BOARD POSITION: Position of Home & Program switches. Press DOWN arrow to view 
the next statistic.
Cycle
Home Switch
Program Switch
Service
Off
Off
Backwash
On
On
Brine Draw/Slow Rinse
On
Off
Fast rinse/Refill
On
On
FLOW METER: Current pulses per second. (K-Factor) - refer to page 63 to varify correct reading. 
Press DOWN arrow to view the next statistic.
AQUASENSOR SUPPLY VOLTAGE:  This will be either PASS or FAIL. If this reading is FAIL
check the Aqua-Sensor connection to the circuit board and to the power supply. Press DOWN 
arrow to view the next statistic.
fw110lt01
may 9 2008
s/n: 00001078
last power up
01-01-08 12:01 pm
system ok
7:32 am 2-1-08
 > 5) adv setup
main board position sensor 
home: off Pos: off
 > 5) diagnostics
 > 2) check sensors
flow meter
7 puls/sec
aquasensor supply voltage
2.5vac: pass
Diagnostics
 
Diagnostics 
56
55
  CULLIGAN GLOBAL ELECTRONIC CONTROLLER