RTU Controllers
ioLogik W5312 Specifications
ioLogik W5340 Specifications
Inputs and Outputs
Digital Inputs: 8 channels
Digital Outputs: 8 channels
Configurable DIOs: 4 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to GND): 
• On: 0 to 3 VDC 
• Off: 10 to 30 VDC
Common Type: 6 points per COM
Counter Frequency: 900 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Inputs and Outputs
Analog Inputs: 4 channels
Configurable DIOs: 8 channels
Relay Outputs: 2 channels
Isolation: 3K VDC or 2K Vrms
Analog Input
Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA
Accuracy: 
• ±0.1% FSR @ 25°C 
• ±0.3% FSR @ -30 and 70°C
Sampling Rate: • All channels: 25 samples/sec 
• Per channel: 6.25 samples/sec 
• Only one channel enabled: 100 samples/sec
Input Impedance: 200K ohms (min.)
Built-in Resistor for Current Input: 102 ohms
Digital Input
Sensor Type: Wet Contact (NPN or PNP) and Dry Contact
I/O Mode: DI or Event Counter
Dry Contact: 
• On: short to GND 
• Off: open
Wet Contact (DI to GND): 
• On: 0 to 3 VDC 
• Off: 10 to 30 VDC
Common Type: 4 points per COM
Counter Frequency:  900 Hz, power off storage
Digital Filtering Time Interval: Software selectable/Programmable
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 160°C (min.)
Current Rating: 200 mA per channel
DIO Output Leakage Current: 3.6 mA @ 24 VDC
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 1 kHz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 160°C (min.)
Current Rating: 200 mA per channel
DIO Output Leakage Current: 3.6 mA @ 24 VDC
Power Requirements
Power Consumption: 
• Always on: 156 mA @ 24 VDC 
• On demand: 138 mA @ 24 VDC
MTBF 
(mean time between failure)
Time: 407,406 hrs
Database: Telcordia (Bellcore)
Relay Output
Type: Form A (N.O.) power relay
Contact Current Rating: 
• Resistive Load: 1 A @ 30 VDC, 250 VAC, 110 VAC
Initial Insulation Resistance: 1000 m ohms (min.) @ 500 VDC
Mechanical endurance: 5,000,000 operations
Electrical endurance: 600,000 operations @ 1 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Power Requirements
Power Consumption: 
ioLogik W5340: 
• Always on: 195 mA @ 24 VDC 
• On demand: 178 mA @ 24 VDC 
ioLogik W5340-HSPA: 
• Always on: 196 mA @ 24 VDC 
• On demand: 189 mA @ 24 VDC
MTBF 
(mean time between failure)
Time: 
ioLogik W5340: 196,561 hrs 
ioLogik W5340-HSPA: 280,739 hrs
Database: Telcordia (Bellcore)