APC NetBotz 320 Rack Appliance NBRK0320E Manual De Usuario

Los códigos de productos
NBRK0320E
Descargar
Página de 210
Basic View: Configuring Appliances
Using Your Appliance
25
Configuring Output Relay Pod 120s
The only configuration tasks that can be performed on a Output Relay Pod 120 using the Basic View are 
specifying a unique identification label for the Output Relay Pod 120, specifying the output type that will 
be used for each relay, and providing a unique identification label for each relay. 
To configure an Output Relay Pod 120 from the Basic View:
1. Click on the Setup button.
2. Select the output control device you wish to configure from the Pods drop-box. A list of available 
output ports on the selected device appears.
3. Select from the Output Type Configured drop-box beside each port the output control action you 
want to assign to the corresponding port. The following output types are available by default:
– None: No output action is associated with this port.
– One-Second Button (NC): When activated, a normally closed (NC) relay is switched to an open 
state for 1 second, and then switched back to closed. 
– One-Second Button (NO): When activated, a normally open (NO) relay is switched to a closed 
state for 1 second, and then switched back to open. 
– Switch (NC): When activated, a normally closed (NC) relay is switched to an open state.
– Switch (NO): When activated, a normally open (NO) relay is switched to a closed state.
– Ten-Second Button (NC): When activated, a normally closed (NC) relay is switched to an open 
state for 10 seconds, and then switched back to closed.
– Ten-Second Button (NO): When activated, a normally open (NO) relay is switched to a closed 
state for 10 seconds, and then switched back to open.
If you have used the Advanced View to define custom output types, your custom output types will 
be available from this list as well.
4. Type in the Port Label field the label that will be used to uniquely identify the device connected to 
output control device port.
5. Click Update to save your output device settings.
Configuring Power Control Pods
You can use the Basic View to specify the Power Control Pod model that you have connected to your 
appliance using a USB-attached serial port device or hub. You can also specify a unique identification 
label for the each Power Control Pod, specify the output type that will be used for each outlet on the pod, 
and providing a unique identification label for each outlet.
To specify the Power Control Pod model that is connected to each serial port:
1. Click on the Setup button.
2. Select the appliance from the Pods drop box in the Setup panel. 
3. Select from the Device Type Installed drop box beside each identified serial port the specific Power 
Note
Before continuing, be sure that you have correctly connected the Output Relay 
Pod 120 to your appliance.