Enlogic EN1119 Hoja De Datos
The Critical Component
LT-50512-A1
Model: EN1119
Specifications
Electrical
Acceptable input voltage
380–415 VAC +6%, -10%
Input current (phase)
16 A
Input frequency
50 Hz
Input power
10.51–11.52 kVA
Input plug
16 A, 5-pin IEC-60309, type 516P6
Input phases
3 phase
Output voltage
100–240 VAC
Maximum output current (phase)
16 A
Maximum output current (outlet)
IEC C13: 10A per outlet, 16A per gang
IEC C19: 16A
IEC C19: 16A
Outlet Configuration
(36)C13, (6)C19
Physical
Dimensions (H x W x D)
173.0 x 5.5 x 4.4 cm
Weight
7.5 Kg
Shipping dimensions (H x W x D)
196.5 x 17.0 x 11.5 cm
Shipping Weight
9.5 Kg
Power cord length
3.0 m (factory standard) or 1.0 – 5.0 m (user specified)
Environmental
Maximum elevation, above MSL (Operating/Storage)
0–3,000 m / 0–15,000 m
Temperature (Operating/Storage)
–5 to 60°C / –25 to 65°C
Humidity (Operating/Storage)
5–95% RH, non-condensing
Compliance
EMC verification
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3
Safety verification
TÜV , CE , EN/IEC 60950-1
Environmental Verification
ROHS, WEEE
EN Series Product Data Sheet