The Critical Component
 
 
 
 
 
      
 
 
 
 
                      
 
LT-50512-A1 
 
 
Model: EN1119 
Specifications
 
Electrical
 
Acceptable input voltage 
 
380–415 VAC +6%, -10%
 
Input current (phase) 
 
16 A 
 
Input frequency 
 
50 Hz
 
Input power 
 
10.51–11.52 kVA
 
Input plug 
16 A, 5-pin IEC-60309, type 516P6
 
Input phases 
3 phase
 
Output voltage 
 
100–240 VAC
 
Maximum output current (phase) 
 
16 A
 
Maximum output current (outlet) 
IEC C13: 10A per outlet, 16A per gang 
IEC C19: 16A 
 
Outlet Configuration 
(36)C13, (6)C19 
 
Physical
 
Dimensions (H x W x D) 
173.0 x 5.5 x 4.4 cm
 
Weight   
7.5 Kg
 
Shipping dimensions (H x W x D) 
 
196.5 x 17.0 x 11.5 cm
 
Shipping Weight  
9.5 Kg
 
Power cord length   
3.0 m (factory standard) or 1.0 – 5.0 m (user specified)
 
Environmental
 
Maximum elevation, above MSL (Operating/Storage) 
0–3,000 m / 0–15,000 m
 
Temperature (Operating/Storage) 
–5 to 60°C / –25 to 65°C
 
Humidity (Operating/Storage)   
5–95% RH, non-condensing
 
Compliance
 
EMC verification 
 
EN 55022 Class A, EN 55024, EN 61000-3-2, EN 61000-3-3
 
Safety verification   
TÜV , CE , EN/IEC 60950-1
 
Environmental Verification
 
ROHS, WEEE
 
 