Greisinger EB 3000 Display, control and monitoring device EB 3000 - 603291 Hoja De Datos

Los códigos de productos
603291
Descargar
Página de 19
E35.0.01.6C-03                     Manual for connection and operation of the EB 3000                        page 11 of 19
7. Error codes
When detecting an operating state which is not permissible, or the current 
EASY
BUS
-measurement channel
has an undefined operating state, the EB3000 will display an appropriate error code.
The following error codes are defined. An errror code will displayed, if an 
EASY
BUS
-measurement channel
with an occurred error is selected.
Err.1:
Exceeding of the measurement range
Indicates that the valid measuring range of the 
EASY
BUS
-measurement channel has been exceeded.
For possible causes and remedies please read the operation manual of the 
EASY
BUS
-sensor mod-
ule
Err.2:
Values below the measuring range
Indicates that the values are below the valid measuring range of the 
EASY
BUS
-measurement channel.
For possible causes and remedies please read the operation manual of the 
EASY
BUS
-sensor mod-
ule
Err.3:
Display range has been exceeded
Indicates that the valid display range (9999 digit) of the device has been exceeded.
Possible causes:
- Incorrect scale.
- Counter overflow.
Remedies:
- The error-message will be reset if the display value is below 9999.
- Reset the counter.
When happening frequently, check the scale-setting, maybe it was set too high and should be reduced
(e.g. factor 10)
Err.4:
Values below display range
Indicates that display value is below the valid display range of the device (-1999 digit).
Possible causes:
- Incorrect scale.
- Counter underflow.
Remedies:
- The error-message will be reset if the display value is above -1999.
- Reset the counter
When happening frequently, check the scale-setting, maybe it was set too low and should be increased
(e.g. factor 10)
Err.7:
System-error
The device features an integrated self-diagnostic-function which checks essential parts of the de-
vice permanently. When detecting a failure, error-message Err.7 will be displayed.
For possible causes and remedies please read the operation manual of the 
EASY
BUS
-sensor mod-
ule
Err.9:
Sensor defective
The device features an integrated diagnostic-function for the connected sensor resp. transmitter.
When detecting a failure, error-message Err.9 will be displayed.
For possible causes and remedies please read the operation manual of the 
EASY
BUS
-sensor
module