Gossen Metrawatt PRÜFKOFFER METRATESTER 5+ 3PVDE-tester VDE 0104 · IEC 61010-1 · VDE 0404 · DIN 43751 · VDI/VDE 3540 · V M 700 K Manual De Usuario

Los códigos de productos
M 700 K
Descargar
Página de 28
22
GMC-I Messtechnik GmbH
10.2
METRATESTER 5+ Test Instrument
Measurements During Operation 
Overload Capacity 
Intrinsic Uncertainty and Measuring Uncertainty 
Reference Conditions
Ambient temp.
+23
C 2 K
Relative humidity
40 
 60%
Line voltage
230 V 
1%
Measured quantity
frequency
50 Hz 
0.2%
Measured quantity
waveshape
Sine (deviation between effective and rectified value: 
0.5%)
Measuring Qty.
Measuring Range
Resolution U
no-load
R
i
I
K
I
N
Protective 
conductor 
resistance
 19.99 
10 m
< 20 V 
> 200 mA
Insulation 
resistance
0.05 
 19.99 M
10 K
600 V 
Approx. 
100 k
< 10 mA >  1  mA
Equivalent 
leakage current,
 19.99 mA 
10
A
28 V 
2 k
< 20 mA —
Contact current 
(verification of 
absence of volt-
age by means of 
current measure-
ment)
 1.999 mA
1
A
2 k
Differential 
current
0,01 
 19.99 mA ~
10
A
Measuring Quantity
Measuring Range
Resolution
Line voltage
207 
 253 V ~
1 V
Load current via mains outlet
 16.00 A ~
10 mA
Load current via mains outlet, differential current 19 A, 5 min.
All other measured quantities
250 V continuous
Measured Quantity
Intrinsic Uncertainty
Measuring Uncertainty
Protective conductor resistance
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)
Insulation resistance, 0 
 19.99 M
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)
Equivalent leakage current
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)
Verification of absence of voltage by means 
of current measurement (contact current)
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)
Differential current
 (4% rdg. + 5 d)
 (10% rdg. + 5 d)
Line Voltage
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)
Load current via mains outlet
 (2.5% rdg. + 2 d)
 (10% rdg. + 5 d)