A-ISOMETER® IR420-D4
Technische Daten IR420-D4..
Isolationskoordination nach IEC 60664-1/IEC 60664-3
Bemessungsspannung ...........................................................................................................  250 V
Bemessungs-Stoßspannung / Verschmutzungsgrad ....................................................  2,5 kV / III
Sichere Trennung (verstärkte Isolierung) zwischen:
............................................................... (A1, A2) - (L1, L2, E, KE, T/R) - (11-12-14) - (21-22-24)
Spannungsprüfung nach IEC 61010-1 ................................................................................. 2,21 kV
Versorgungsspannung
IR420-D4-1:
Versorgungsspannung U
s
 ....................................................................  AC 16...72 V / DC 9,6...94 V
Frequenzbereich U
s
 ................................................................................................  42...460 Hz / DC
IR420-D4-2:
Versorgungsspannung U
s
 ..................................................................................... AC/DC 70...300 V
Frequenzbereich U
s
 .................................................................................................. 42...460 Hz, DC
Eigenverbrauch .....................................................................................................................  
 3 VA
Überwachtes IT-System
Netznennspannung U
n
 ................................................................................................ AC 0... 300 V
Nennfrequenz f
n
 .............................................................................................................  42...460 Hz
Ansprechwerte
Ansprechwert R
an1
 (ALARM 1)  ...................................................................................... 1...200 k
Ω
Ansprechwert R
an2
 (ALARM 2)  ...................................................................................... 1...200 k
Ω
Preset-Funktion:
U
n
 
 72 V: R
an1
 (ALARM 1)/ R
an2
 (ALARM 2) ........................................................ 20 k
Ω / 10 kΩ
U
n
 
>
 72 V: R
an1
 (ALARM 1)/ R
an2
 (ALARM 2) ........................................................ 46 k
Ω / 23 kΩ
Ansprechabweichung (1...5 k
Ω) / (5...200 kΩ) ............................................. 
±
0,5 k
Ω / 
±
15 %
Hysterese (1...5 k
Ω) / (5...200 kΩ) .................................................................. +1 kΩ /  +25 %
Zeitverhalten
Ansprechzeit t
an
 bei R
F
 = 0,5 x R
an
 und C
e
 = 1 µF .................................................................  
 1 s
Anlaufverzögerung t .............................................................................................................  0...10 s
Ansprechverzögerung t
on
 .....................................................................................................  0...99 s
Messkreis
Messspannung U
m
.................................................................................................................. 
±
12 V
Messstrom I
m
  (bei R
F
 = 0
Ω).......................................................................................... 
 200 
μA
Innenwiderstand DC R
i
....................................................................................................... 
 62 k
Ω
Impedanz Z
i
 bei 50 Hz ........................................................................................................ 
 60 k
Ω
Zulässige Fremdgleichspannung U
fg
.............................................................................  
 DC 300 V
Zulässige Netzableitkapazität C
e
..........................................................................................  
 20 µF
Anzeigen, Speicher
Anzeige .........................................................................  LC-Display, multifunktional, unbeleuchtet
Anzeigebereich Messwert ..........................................................................................  1 k
Ω...1 MΩ
Betriebsmessabweichung (1...5 k
Ω) ..............................................................................  
±
0,5 k
Ω
Betriebsmessabweichung (5 k
Ω...1 MΩ) ..........................................................................  
±
15 %
Passwort ......................................................................................................................... off / 0...999
Fehlerspeicher (Alarmrelais)  ................................................................................................ on / off
Eingänge
Leitungslänge  externe Test- / Reset-Taste ......................................................................... 
≤ 10 m
Schaltglieder
Anzahl ..............................................................................................................  2 (Wechsler K1, K2)
Arbeitsweise ...........................................................................................  Ruhestrom / Arbeitsstrom
Elektrische Lebensdauer bei Bemessungsbedingungen ................................... 10000 Schaltspiele
Kontaktdaten nach IEC 60947-5-1:
Bemessungsbetriebsspannung AC ....................................................................... 230 V.......  230 V
Gebrauchskategorie AC  ........................................................................................ AC 13.......  AC 14
Bemessungsbetriebsstrom AC  .................................................................................  5 A............ 3 A
Bemessungsbetriebsspannung DC  ...................................................  220 V ....... 110 V.......... 24 V
Gebrauchskategorie DC  .....................................................................  DC 12 ....... DC 12.......  DC 12
Bemessungsbetriebsstrom DC  ...........................................................  0,1 A ........ 0,2 A............ 1 A
Mindeststrom ..............................................................................................1 mA bei AC/DC 
≥ 10 V
Technical data IR420-D4..
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Rated insulation voltage........................................................................................................... 250 V
Rated impulse voltage / Pollution degree ........................................................................ 2.5 kV / III
Protective separation (reinforced insulation) between:
.............................................................. (A1, A2) - (L1, L2, E, KE, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test acc. IEC 61010-1  .............................................................................................. 2.21 kV
Supply voltage
IR420-D4-1:
Supply voltage U
s
  ................................................................................  AC 16...72 V / DC 9.6...94 V
Frequency range U
s
 ................................................................................................ 42...460 Hz / DC
IR420-D4-2:
Supply voltage U
s
  ................................................................................................. AC/DC 70...300 V
Frequency range U
s
 .................................................................................................  42...460 Hz, DC
Power consumption ..............................................................................................................  
≤ 3 VA
IT System being monitored
Nominal system voltage U
n
.........................................................................................  AC 0... 300 V
Nominal frequency f
n
.....................................................................................................  42...460 Hz
Response values
Response value R
an1
 (ALARM 1).............................................................................. 1 k
Ω...200 kΩ
Response value R
an1
 (ALARM 2).............................................................................. 1 k
Ω...200 kΩ
Preset function:
U
n
 
 72 V: R
an1
 (ALARM 1)/ R
an2
 (ALARM 2) ........................................................  20 k
Ω / 10 kΩ
U
n
 
>
 72 V: R
an1
 (ALARM 1)/ R
an2
 (ALARM 2) ........................................................  46 k
Ω / 23 kΩ
Operating error (1...5 k
Ω) / (5...200 kΩ) 
........................................... ±
0.5 k
Ω / 
±
15 %
Hysteresis (1...5 k
Ω) / (5...200 kΩ) ....................................................................+1 kΩ / +25 %
Time response
Response time  t
an
 at R
F
 = 0,5 x R
an
 and C
e
 = 1 µF ................................................................ 
≤ 1 s
Starting delay t  ...................................................................................................................... 0...10 s
Response delay t
on
 ................................................................................................................ 0...99 s
Measuring circuit
Measuring voltage U
m
............................................................................................................. 
±
12 V
Measuring current I
m
   (R
F
 = 0
Ω) ..................................................................................  
 200 
μA
Internal d.c. resistance R
i
....................................................................................................  
 62 k
Ω
Internal impedance Z
i
 (50 Hz) ...........................................................................................  
 60 k
Ω
Admissible extraneous d.c. voltage U
fg
.........................................................................  
 DC 300 V
System leakage capacitance C
e
............................................................................................  
 20 µF
Displays, memory
Display...................................................................... LC display, multi-functional, non-illuminated
Display range, measuring value ................................................................................  1 k
Ω...1 MΩ
Operating error (1...5 k
Ω) ................................................................................................ 
±
0.5 k
Ω
Percentage operating error (5 k
Ω...1 MΩ) ........................................................................ 
±
15 %
Password ........................................................................................................................  off / 0...999
Fault memory (alarm relay)  .................................................................................................  on / off
Inputs
Cable length external test / reset button.............................................................................. 
 10 m
Switching elements
Number of.......................................................................................  2 (changeover contacts K1, K2)
Operating principle....................................................................... (N/O operation) (N/C operation)
Electrical endurance ............................................................................ 10000 switching operations
Contact data according IEC 60947-5-1
Rated operational voltage AC ...............................................................................  230 V ....... 230 V
Utilization category AC   ........................................................................................  AC 13 ....... AC 14
Rated operational current AC   ..................................................................................  5 A ........... 3 A
Rated operational voltage DC  ............................................................ 220 V.......  110 V ......... 24 V
Utilization category DC   ...................................................................... DC 12........ DC 12 ....... DC 12
Rated operational current  DC   ............................................................ 0.1 A........  0.2 A ........... 1 A
Minimum current ..........................................................................................1 mA at AC/DC 
≥ 10 V