Operation and setting
18
5.4
Display in standard mode
By default, the currently measured residual current is displayed. The current 
response values I1 (prewarning) and I2 (alarm) can be displayed using the Up 
and Down key. Press the Enter key to return to the measured value.
t
(timing 
check)
t on 1
-
Response delay K1
t on 2
-
Response delay K2
t
-
Starting  delay
t off
-
Delay on release K1/K2
Set
(device con-
trol)
I 12
HI
Selectable parameters:
High, window function, low
off
Parameter setting via pass-
word
FAC
-
Restore factory settings
SYS
-
Function blocked
InF
-
Display hard / software ver-
sion
HiS
Clr
-
History memory for the first 
alarm value, erasable
In the standard mode, the currently set response values I1 and I2
can be displayed using the Up and Down keys.
Menu
Sub
Menu
Menu 
item
Activa-
tion
Adjustable parameter