Bender VMD4105-D-2 B93010045 Hoja De Datos

Los códigos de productos
B93010045
Descargar
Página de 64
Function
16
3.2.5
Malfunction and messages
In the case of an internal malfunction or an error in the operation of the cou-
pling switches, both alarm LEDs will flash. The error code or the message in 
plain text is indicated on the display. 
If several faults or messages occur simultaneously, they will be displayed alter-
nately at four-second-intervals.
In the case of an internal error, make a note of the error code "xx" and contact 
the Bender Service.
In case of malfunctions or messages, the power
generation system will be separated from the supply
network.
Code/
Message
LED
Meaning
Remedy
1…20
Both LEDs
flash
Internal error
Make a note from the error 
code "xx“ and contact the 
Bender Service.
contact 
monit. K1
Both LEDs
flash
Error: 
Contact 
monitoring 
K1
After rectifying the the fault 
at the coupling switch/main 
switch (e.g. manual connec-
tion of the backup switch), 
the fault is automatically 
cleared. Should, however, a 
fault have occurred three 
times within 30 seconds, nor-
mal operation must be 
started again after fault recti-
fication by pressing the 
"RESET" button (in the stand-
ard display).
contact 
monit. K2
Error: 
Contact 
monitoring 
K2