Bender VMD4105-D-2 B93010045 Hoja De Datos

Los códigos de productos
B93010045
Descargar
Página de 64
Installation, connection and commissioning
27
4.8.3
Details regarding the digital inputs (D1…D4, RT1)
Fig. 4.5: Block diagram (simplified representation)
4.9
Standards, selectable
The VMD460-NA includes the following standards:
 
VDE-AR-N 4105
 
CEI 0-21
 
BDEW 
 
C10/11
Menu: "Settings" --> "General" --> "Norm".
4.10 Commissioning
Danger of electric shock!
Improper connection can lead to injury to persons and damage
to the device! 
Prior to commissioning make sure that the device is properly
connected
!
low  : < 4 V DC
high : > 6 V DC
U
max
 = 30 V DC
D1
Dx
GND
12V
R1
DC
Source
I < 5 mA
Open
Collector
DGx
µC
Relais
Kontakt
Q1
V1
24
1
2
Dx:  
D1, D2, D3, D4, RT1
DGx:   DG1/2, DG3/4, RTG