Bender VMD4105-D-2 B93010045 Hoja De Datos

Los códigos de productos
B93010045
Descargar
Página de 64
Operation and configuration
35
Measuring channel 15: Indicates the total time passed during the self test 
between the simulation of 0 V on L1 to the disconnection of coupling 
switch 1.
Measuring channel 16: Indicates the total time passed during the self test 
between the simulation of 0 V on L1 to the disconnection command for 
coupling switch 1.
** not used
5.4.2
History
The fail-safe history memory stores up to 300 events (alarms, tests) with infor-
mation about alarms and acknowledgements and the time the event hap-
pened. If the history memory is full, the oldest entry will be deleted in the 
event of an alarm to create space for the new entry (FIFO principle).
For details about erasing the entire history memory manually, refer to 
"Chapter 5.4.4 System" on page 38.
Fig. 5.6: History (overview)
Key
Line 1: Event number
Line 2: Event start: Date/time
Line 3: Acknowledgement of the event: Date/time
Line 4: Event end: Date/time
Possibilities:
1. If you are searching for an event that occurred at a specific time, use the 
arrow buttons to scroll to the required entry.
2. Call up details: Use the 
 button to call up the current history memory 
entry.
 History No. 297
 Start: 01.02.13 / 15:57:00
 Quit:
 End: 01.02.13 / 16:07:03