4.3 Execution of the user program 
 
Easy Book 
56
 
Manual, 03/2014, A5E02486774-AF 
Consider the following two cases where interrupt events trigger a cyclic OB and a time delay 
OB. In both cases, the time delay OB (OB201) has no process image partition assignment 
and executes at priority 4. The cyclic OB (OB200) has a process image partition assignment 
of PIP1 and executes at priority 2. The following illustrations show the difference in execution 
between non-interruptible and interruptible execution modes: 
 
Figure 4-1 
Case 1: Non-interruptible OB execution 
 
Figure 4-2 
Case 2: Interruptible OB execution 
 
 
Note 
If you configure the OB execution mode to be non-interruptible, then a time error OB cannot 
interrupt OBs other than program cycle OBs. Prior to V4.0 of the S7-1200 CPU, a time error 
OB could interrupt any executing OB. With V4.0, you must configure OB execution to be 
interruptible if you want a time error OB (or any other higher priority OB) to be able to 
interrupt executing OBs that are not program cycle OBs. 
 
Understanding event execution priorities and queuing 
The number of pending (queued) events from a single source is limited, using a different 
queue for each event type. Upon reaching the limit of pending events for a given event type, 
the next event is lost. Refer to the topic about time error interrupt OBs for more information 
regarding queue overflows. 
Each CPU event has an associated priority. In general, the CPU services events in order of 
priority (highest priority first). The CPU services events of the same priority on a "first-come, 
first-served" basis.