Brocade Communications Systems Brocade Backbone DCX 8510-4 Manual De Usuario

Descargar
Página de 168
116
Brocade DCX 8510-4 Backbone Hardware Reference Manual
53-1002177-05
Power cords
A
Power supply redundancy is key to your installation, so any demand must be met with twice the 
capacity. See 
 for power supply requirements for specific demand ranges.
In addition to these tables, you can consult the power tables in the latest update of the Fabric OS 
Release Notes.
Power cords
The types of power cords provided with the Brocade DCX 8510-4 are specific to the country where it 
is installed. For each of the types of power cords in 
, the end that connects to the Brocade 
DCX 8510-4 has an IEC 60320/C19 cable connector. The AC power receptacles on each power 
supply are equipped with IEC 60320/C20 power connectors.
In order to connect to a power strip already installed in a cabinet, the C20, 20A-250V, 12 AWG 
power cord is required.
To order a power cord, contact your Brocade DCX 8510-4 supplier.
FX8-24
250
Extension 
blade
12 8 Gbps SFP+
10 1 Gbps Ethernet
2 10 Gbps Ethernet
up to 4
48 8 Gbps
40 1 Gbps Ethernet
8 10 Gbps Ethernet
Fan unit
90
NA
NA
2 fans per chassis
NA
TABLE 20
Power supply requirements
Demand
power supplies @ 110 
VAC (nominal)
power supplies @ 220 
VAC (nominal)
up to 1000W
2
2
1000W-2000W
NA - cannot achieve 
redundancy
2
greater than 2000W
NA - cannot achieve 
redundancy
NA - cannot achieve 
redundancy
TABLE 19
Power demands per component  (Continued)
Blade or fan 
units
Maximum 
Power Draw 
(Watts)
Type of Blade Ports per blade
Number of blades 
permitted in chassis
Total ports per chassis