The IM 154-2 DP High Feature interface module is responsible
for PROFIBUS communication between the ET 200pro station
and the host automation system (controller) as PROFIBUS DP
master. The scope of delivery of the interface module also in-
cludes a terminating module which is plugged in following the
last electronics module of the station.
■
Function
Features of the IM 154-2 DP High Feature interface module
• Mounted on delivery on the bus module
• Connects the ET 200pro station to the PROFIBUS DP via the
• Connects the ET 200pro station to the PROFIBUS DP via the
connection module
• Prepares the data for the connected electronics modules
• Max. 16 electronics modules can be operated on an interface
• Max. 16 electronics modules can be operated on an interface
module - also safety-related
• PROFIBUS DP address of the ET 200pro station can be set on
the connection module
• Terminating resistor of the PROFIBUS DP can be switched on
and off on the connection module
• Maximum address range: 244 bytes for inputs and 244 bytes
for outputs
• Powers the ET 200pro station via the connection module with
the sensor/electronics supply 1L+ and the load power supply
2L+
• Integral power module for the load power supply 2L+
■
Technical specifications
For detailed technical specifications of the interface module,
see:
• Catalog IK PI
• Mall/CA 01 under "Distributed I/Os / ET 200pro"
• Catalog IK PI
• Mall/CA 01 under "Distributed I/Os / ET 200pro"
■
Accessories
Connection modules
The connection module for the IM 154-2 DP High Feature inter-
face module (to be ordered separately) is available in three dif-
ferent connection versions:
• CM IM DP direct
• CM IM DP ECOFAST Cu
• CM IM DP M12 7/8"
The PROFIBUS address can be set on the connection module
• CM IM DP direct
• CM IM DP ECOFAST Cu
• CM IM DP M12 7/8"
The PROFIBUS address can be set on the connection module
per DIL switch. The segmenting terminating resistor can be con-
nected using a further DIL switch.
■
Selection and Ordering Data
Order No.
IM154-2 High Feature interface
module
module
for ET 200pro; for communication
between ET 200pro and host
masters over PROFIBUS DP; sup-
port of PROFIsafe
6ES7 154-2AA00-0AB0
B)
Connection module for IM154-2
High Feature interface module
High Feature interface module
• CM IM DP ECOFAST connection
module
for connection of PROFIBUS DP
and 24 V DC power supply to
PROFIBUS interface modules,
2 ECOFAST Cu connections
6ES7 194-4AA00-0AA0
B)
• CM IM DP direct connection
module
for direct connection of
PROFIBUS DP and 24 V DC
power supply to PROFIBUS in-
terface modules, up to six M20
cable glands
6ES7 194-4AC00-0AA0
B)
• CM IM DP M12 7/8" connection
module
for connection of PROFIBUS DP
and 24 V DC power supply to
PROFIBUS interface modules,
2 x M12 and 2 x 7/8"
6ES7 194-4AD00-0AA0
B)
Cables and further accessories
For cables and further accesso-
ries for CM IM DP ECOFAST,
CM IM DP direct and CM IM DP
M12 7/8" connection modules,
see Catalog IK PI or Mall/CA 01
under "Distributed I/O /
ET 200pro"
General accessories
ET 200pro module support
• Narrow, for interface, electronics
and power modules
- 500 mm
- 500 mm
6ES7 194-4GA00-0AA0
- 1000 mm
6ES7 194-4GA60-0AA0
- 2000 mm, can be cut to length
6ES7 194-4GA20-0AA0
• Compact-narrow, for interface,
electronics and power modules
- 500 mm
- 500 mm
6ES7 194-4GC70-0AA0
- 1000 mm
6ES7 194-4GC60-0AA0
- 2000 mm, can be cut to length
6ES7 194-4GC20-0AA0
Spare fuse
12.5 A fast-blow, for interface and
power modules, 10 units per pack
6ES7 194-4HB00-0AA0
B) Subject to export regulations: AL: N, ECCN: EAR99H