Siemens FC700A Manual De Usuario
Technical data FC700A
12
Siemens Building Technologies
007836_a_en_--.doc
Fire & Security Products
03.2004
4
Technical data FC700A
Operating voltage
115 / 230VAC
±15%
50... 60Hz
Power consumption
40... 220VA (per converter B2F020)
Battery operation in the event of mains failure
- Standard operating period
- Optional
- Optional
12...24h
Up to 72h (see chapter 23)
Up to 72h (see chapter 23)
Environmental conditions
Temperature during
operation
Storage
Humidity
0°C... +40°C
-20°C... +60°C
Max. 95%, no condensation
Complies with class 3K5 according to IEC 721–3–3
-20°C... +60°C
Max. 95%, no condensation
Complies with class 3K5 according to IEC 721–3–3
IP protection category (EN 60529 / IEC 529)
- Control unit
- Remote control terminal
- Remote control terminal
IP50
IP52 H26G220
IP52 H26G220
cabinet
IP40 H28G200
cabinet
Dimensions
- Control unit cabinet
- Separate control terminal
- Separate control terminal
in cabinet H26G220
H28G200
W =
520mm,
H = 602mm,
D = 100mm / 155mm
W = 366mm,
H = 219mm,
D = 76mm
W = 520mm,
H = 300mm,
D = 70mm
Colors
- Control unit cabinet
- Operating unit front terminal B3Q700
- Control terminal cabinet
- Operating unit front terminal B3Q700
- Control terminal cabinet
H26G220
H28G200
H28T110/120
RAL 7035 light grey
Dark grey like Pantone 431C, Pantone 429C grey
Pantone 421 grey
RAL 7035 light grey
1E110 dark grey
Dark grey like Pantone 431C, Pantone 429C grey
Pantone 421 grey
RAL 7035 light grey
1E110 dark grey