NIM Primitives
4-25
SIMATIC TIWAY I Series 500 NIM User Manual
Table 4-5
Data Element Address Ranges
P/C Type
Data Type
520–
1101
530–
1102
530–
1104
530–
1108
520C
–1101
520C
–1102
530C
–1104
530C
–1108
530C
–1112
560–
1101
565–
1101
NOTE
L Instruction
TT = 00
1024
2048
4095
8191
   *
1024
2048
4096
8192
12000
8192
8192
B
V Variable
TT = 01
512
1024
1024
2048
512
1024
2048
4096
5120
2048
2048
B
K Constant
TT = 02
0
0
0
0
0
0
0
0
0
0
0
A,B
Discrete I/O
X,Y,X&Y Packed
TT = 3,4,6,7
128
1023
1023
1023
1023
1023
1023
1023
1023
2048
2048
B
Control Register
CR, CR Packed
TT = 5,8
256
511
511
511
255
511
511
511
1023
2048
2048
B
Word I/O
WX, WY
TT = 9,A
128
1023
1023
1023
1023
1023
1023
1023
1023
2048
2048
B
Discrete Force
TT = 0B
128
1023
1023
1023
1023
1023
1023
1023
1023
2048
2048
B
CR Force
TT = 0C
256
511
511
511
255
511
511
511
1023
2048
2048
B
Word Force
TT = 0D
128
1023
1023
1023
1023
1023
1023
1023
1023
2048
2048
B
Timer/Counter
TCC/TCP
TT = E,F
128
255
255
255
60
256
256
256
400
1024
1024
B
Drum Step
DSP, DSC, DCP
TT = 10,11,12
10
30
30
30
15
30
30
30
30
128
128
B,D
System Status
TT = 17
1
1
1
1
1
1
1
1
1
1
1
B
Loop Data
TT = 20–35 and
60–75
0
0
0
0
0
0
0
0
0
0
64
A,B
Ramp/Soak Data
TT = 36–3B
0
0
0
0
0
0
0
0
0
0
255
B,C
Analog Alarm
TT = 3C–4A and
7C–8A
0
0
0
0
0
0
0
0
0
0
128
A,B
Notes:
A)
Entry of zero is a non-supported or non-configured Data Type for the P/C.
B)
560 and 565 data sizes are default values for a minimal system configuration. All of these values (except loops, analog
alarms and system status) can be reconfigured.
C)
There are 255 ramp/soak steps for each loop in a 565.
D)
There are 16 steps for each event drum in a P/C.
Read only (L-memory in EPROM only).