6 Configuring and Programming the CP as a PROFINET IO Device
B3L−25
CP 343-1 Lean for Industrial Ethernet / Manual Part B3L
Release 03/2007
C79000-G8976-C198-04
C79000-G8976-C198-04
Result:
You will see the connector symbol for the PROFINET IO system beside the
PROFINET IO controller.
Step 2: Configuring the PROFINET IO device on the PROFINET IO controller
1. Open the hardware catalog and select a version of the CP V2.0 or higher as the
PROFINET IO device from the folder “PROFINET IO”
"
“I/O”
"
“SIMATIC S7−CP”
"
“CP 343−1 Lean”.
2. Connect the CP with the PROFINET IO system (drag and drop).
3. Add input and output modules with the required I/O data length (1 to max. 240
3. Add input and output modules with the required I/O data length (1 to max. 240
bytes) to the PROFINET IO device.
The following screenshot shows the configuration table of the PROFINET IO
controller with an S7−400 station as PROFINET IO controller. The PROFINET IO
device shown here, for example, has three modules for process inputs (I address)
and process outputs (O address).
controller with an S7−400 station as PROFINET IO controller. The PROFINET IO
device shown here, for example, has three modules for process inputs (I address)
and process outputs (O address).
Figure 6-4
SIMATIC Station with PROFINET IO System with the CP as Device with Input (DI) and
Output Modules (DO)