DR4300 Circular Chart Recorder 
102 
DR4300 Circular Chart Recorder Product Manual 
12/03 
Lower Display 
Prompt 
Upper Display  
Range of Setting  
or Selection 
Parameter  
Definition 
RATE T
 
0.08 to 10.00 minutes 
0.08 or less = OFF 
 
[factory setting = 0.0] 
 
RATE—Rate action affects the recorder’s output 
whenever the deviation between setpoint and process 
variable is changing. It affects it more when the deviation 
is changing faster. (This is the “derivative” component of 
control.)  
ATTENTION
 If control group parameter “OUTALG” 
is “RLYD” (relay duplex), “Tcur” (time/current duplex), or 
“CurT” (current/time duplex), and you are using the 
recorder in a heat/cool application, RATE T is used for 
heat control. Cooling control would use RATE2T 
described later in this table. 
I MIN 
or 
I RPM 
 
0.02 to 50.00 
 
[factory setting = 0.02]
 
RESET IN MINUTES PER REPEAT or RESET IN 
REPEATS PER MINUTE—Which of these prompts is 
displayed depends on the selection made for control 
group parameter “MINRPM”.  
Reset adjusts the recorder’s output taking into 
consideration both the size of the deviation (SP-PV) and 
the duration of the deviation. (This is the “integral” 
component of control.) The amount of corrective action 
depends on the value of PB or GAIN.   
The reset value specified here determines how many 
times proportional action is repeated per minute  
(I RPM) or the length (in minutes) of the reset action (I 
MIN). For example, if I MIN = .5, it is the same as if I 
RPM = 2. The result is the same; two resets are 
performed in every minute. 
ATTENTION
 If control group parameter “OUTALG” 
is “RLYD” (relay duplex), “Tcur” (time/current duplex), or 
“CurT” (current/time duplex), and you are using the 
recorder in a heat/cool application, I MIN or I RPM is 
used for heat control. Cooling control would use I2 MIN 
or I2 RPM described later in this table. 
MANRST 
–100 to +100 (in % output) 
 [factory setting = 0]
 
 
MANUAL RESET—This parameter is only applicable if 
control group parameter “CTRALG” is “PDMR”  
(PD with manual reset). Because a proportional recorder 
will not necessarily line out at setpoint, there will be a 
deviation (offset) from setpoint. This reset value can be 
used to eliminate the offset and lets the PV line out at 
setpoint. The controller output is the computed output 
plus the value of MANRST.