Eclipse Combustion 6500 Manual De Usuario
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
13
S2 DIP Switches
The S2 DIP switches permit programming of timing and sequence
functions of the Bi-Flame.
functions of the Bi-Flame.
Note:
The S2 DIP switch settings at left are for illustrative purposes
only; the actual settings of any of these switches will be
determined by your system conditions.
The S2 DIP switch settings at left are for illustrative purposes
only; the actual settings of any of these switches will be
determined by your system conditions.
SW1: Recycling mode selection (On=Recycling; Off=Non-recycling)
SW2: Pilot selection (On = Intermittent, where pilot remains on during
burner cycle; Off = Interrupted, where pilot valve closes after main
burner is established).
burner cycle; Off = Interrupted, where pilot valve closes after main
burner is established).
SW3: Trial-for-ignition (TFI) range selection; used with SW7 of the S4
DIP switch. See the table at left for proper selection.
DIP switch. See the table at left for proper selection.
SW4 through 8: Purge time selection; switch in off position selects
indicated purge time. Selected purge times are additive. See
illustration at left for exact times.
indicated purge time. Selected purge times are additive. See
illustration at left for exact times.
S4 DIP Switches
SW1: Fan operation on flame failure (on = fan turns off; off = fan stays
on).
on).
SW5: Leak test time (on=110 seconds; off=40 seconds).
SW7: Trial-for-ignition (TFI) range selection; used with SW3 of the S2
DIP switches. See the table at left for proper selection.
DIP switches. See the table at left for proper selection.
SW8: Purge mode; (on = modulation, off = process).
S6 DIP Switches
The S6 DIP switches are factory set for two burners. DO NOT
CHANGE. Any other setting will result in an “UNMATCH#” fault
condition.
CHANGE. Any other setting will result in an “UNMATCH#” fault
condition.
DIP
SWITCH
SETTINGS
SW6: Off, Not used.
SW7: Off, Not used.
SW8: Frequency Selection; (On = 50Hz, Off = 60 Hz)
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
50/60Hz
—
—
—
MOD/PROC
TFI
—
LEAK 110/40
—
—
—
—
—
BLOWER
Number
of
PAF
P
U
R
G
E
X4
120/8
60/4
30/2
15/1
30/2
15/1
TFI
PILOT IMIT/IRPT
RECYCLE
S6
S4
S2
8
7
6
5
4
7
6
5
4
X4
120 sec.
60 sec.
30 sec.
15 sec.
30 sec.
15 sec.
ON
OFF
—
Time
Not
Added
S2 Modulation Purge Time, S4 - 8 = ON
8
7
6
5
4
7
6
5
4
X4
8 min.
4 min.
2 min.
1 min.
4 min.
2 min.
1 min.
ON
OFF
—
Time
Not
Added
S2 Process Purge Time, S4 - 8 = OFF
ON/OFF
DIP Switch Functions
Trial-for-Ignition (TFI) Settings
If the
TFI
needed is:
5 seconds
10 seconds
15 seconds
THEN
SW3 of S2
DIP switch
must be
turned:
Off
Off
On
AND
SW7 of S4
DIP Switch
must be
turned:
Off
On
Off or On