Eclipse Combustion 6500 Manual De Usuario

Descargar
Página de 46
Eclipse Bi-Flame v1.8, Instruction Manual 826, 05/03
26
Figure 6.2
  Wiring Diagram & Connections –Main Chassis
On/Off
Alarm
Fan Motor
Interlocks & Limits
Air Flow
120 VAC
POVC
15 A. Fuse
6
7
8
9
10
1
2
3
5
4
Low Fire
High Fire
6
7
8
1
2
3
5
4
MS
  Aux. Input #41
  Aux. Input #31
  Aux. Input #21
  Aux. Input #11
  Leak Detect
Neutral
Main
   Leak Detect
Pilot
Ignition 
1
2
3
4
Flame Rod
Shield
Blue
5600-90A
or 5600-91
U.V. Scanner
Yellow 
Main Gas Valve
Block Valve
Pilot Gas Valve
Neutral
J1
Terminals
J2
Terminals
J4
  Terminals2
J5
  Terminals2
Burner #1
1
2
3
4
Flame Rod
Shield
Yellow
Blue 
Burner #2
6
5
4
3
1
2
RS 232
Rx
Tx
Remote
Reset
Pushbutton
(if required)
VDK/VLSD
J7
Terminals
When not used, must be tied into 120 VAC. 
1
Using both sensors isn’t mandatory; you may use a flame rod, or a UV scanner, or both.
2
J1 (Input) Terminals
  1  –  Limits Input
  2  –  Air Switch Input
  3  –  POVC Switch Input
  4  –  Low Fire Switch Input
  5  –  High Fire Switch Input
  6  –  VDK/VLDS Input
  7  –  Aux. #11
  8  –  Aux. #21
  9  –  Aux. #31
10  –  Aux. #41
J7 (Interface) Terminals
Auxiliary
Inputs
  1  –  Flame Rod
  2  –  Ground (Yellow)
  3  –  U.V. (Blue)
  4  –  Shield Connection
  1  –  U.V. (Blue)
  2  –  Ground (Yellow)
  3  –  Flame Rod
  4  –  Shield Connection
J2 (Output) Terminals
  1  –  Neutral
  2  –  120 VAC
  3  –  Fan
  4  –  Main Gas Valve
  5  –  Pilot Gas Valve
  6  –  Ignition Transformer
  7  –  VDK/VLSD
  8  –  Alarm
Bi-Flame
Power Inputs
Outputs
J3 (Modulation) Terminals
  1  –  Common
  2  –  Auto
  3  –  Hi Fire
  4  –  Low Fire
Modulation
Motor
Connections
for High Fire &
Low Fire Start
J4 (Sensors/Burners 1 & 3) Terminals
2
Burner #1
J5 (Sensors/Burners 2 & 4) Terminals
2
Burner #2
  6  –  RS 232/RS 485 Interface
  5  –  RS 232/RS 485 Interface
  4  –  Reset
  3  –  Scan
  2  –  Enter
  1  –  Ground
5600-90A
or 5600-91
U.V. Scanner
GND (Return)
D
C
A
B
Signal (UV)
Neutral
120 VAC
5602-91
U.V.
Self-Check
Scanner
VDK/VLSD
Customer Supplied (if used)
1
2
3
4
Common
Auto
High Fire
Low Fire
J3
Terminals
P1-1
P1-2
P1-4
+
-
ACT004
Temperature
Controller
4 to 20 mA
Ignition Coil
Ignition Coil